TRANSPORT – HANDLING – WARNING
DELIVERY CHECKS
On receipt of a new equipment please check the following
points. It is the customer's responsibility to ensure that the
products are in good working order:
- The exterior has not been damaged in any way.
- The lif ting and handling equipment are suitable for the
equipment and comply with the specif ications of the
handling instructions enclosed here-in.
- Accessories ordered f or on site installation hav e been
deliv ered and are in good working order.
- The equipment supplied corresponds to the order and
matches the delivery note.
If the product is damaged, exact details must be confirmed
in writing by registered post to the shipping company
within 48 hours of delivery (working days). A copy of the
letter must be addressed to Lennox and the supplier or
distributor f or inf ormation purposes. Failure to comply will
inv alidate any claim against the shipping company.
RATING PLATE
The rating plate prov ides a complete reference for the
model and ensures that the unit corresponds to the model
ordered. It states the electrical power consumption of the
unit on start-up, its rated power and its supply v oltage. The
supply v oltage must not dev iate bey ond +10/-15 %. The
start-up power is the maximum value likely to be achiev ed
f or the specif ied operational v oltage. The customer must
hav e a suitable electrical supply. It is theref ore important to
check whether the supply v oltage stated on the unit's
rating plate is compatible with that of the mains electrical
supply . The rating plate also states the year of
manuf acture as well as the ty pe of ref rigerant used and the
required charge for each compressor circuit.
IOM – FLEXY II – 1007 – E
STOR AGE
When units are deliv ered on site they are not alway s
required immediately and are sometimes put into storage.
In the event of medium to long-term storage, we
recommend the f ollowing procedures:
- Ensure that there is no water in the hydraulic systems.
- Keep the heat exchanger covers in position (AQUILUX
cover).
- Keep protective plastic film in position.
- Ensure the electrical panels are closed.
- Keep all items and options supplied in a dry and clean
place f or f uture assembly bef ore using the equipment.
MAINTENANCE KEY
On deliv ery we recommend that you keep the key which is
attached to an ey ebolt in a safe and accessible place. This
allows y ou to open the panels f or maintenance and
installation work.
The locks are ¼ turn + then tighter (figure 2).
CONDENSATE DRAINS
The condensate drains are not assembled when deliv ered
and are stored
in the electrical panel with their clamping collars.
To assemble them, insert them on the condensate tray outlets
and use a screwdriver to tighten the collars (Figure 3).
Fig. 1