Nortel 1000E Maintenance Manual page 72

Communication server
Hide thumbs Also See for 1000E:
Table of Contents

Advertisement

Page 72 of 162
Clearing faults
Table 12
Call Server faults (Part 3 of 5)
Condition
Possible cause
CD-ROM
CD-ROM disk is
drive not
damaged
reading disk
CD-ROM
Defective CD-ROM
drive not
drive
operating
Fan LED or
High room
temperature
temperature
LED is red
Defective alarm/fan
module
Power supply air
filter is obstructed
553-3041-500
Standard 1.00
If you have another CD-ROM disk, insert that CD-ROM
disk into a known operational Drive Carrier card, and
load the Software Installation Tool from the correct
Install Program diskette.
In the Software Installation Tool, go to the Tools Menu
and select option:
<j> -To check the customer-specific part
of the CD-ROM
If the test is successful, it is unlikely the CD-ROM disk is
damaged.
However, if the test indicates a failure to read all files on
the CD-ROM disk, then the CD-ROM disk is damaged
and must be replaced.
Remove the CD-ROM disk from the CD-ROM drive,
place it in the CD-ROM drive of the other Call Server,
and test operation.
If the CD-ROM disk is operational, replace the Drive
Carrier card containing the faulty CD-ROM drive.
Adjust room temperature as necessary. Allow the
system to cool for a few minutes, then reset the system.
Verify that the fans in the alarm fan/module are
operational.
Unseat and re-install alarm/fan module. If the fault
continues, replace the alarm/fan module.
Check filter to ensure it is clean. If the filter is dirty or
damaged, clean or replace the filter as described in
"Cleaning and replacing the power supply air filter" on
page
123.
September 2004
Action