6. The pole pair number of the motor is displayed grayed-out in the opened dialog. This
value must be considered for the input of the gear ratio. No mechanical gearbox is used
in the example. Consequently, the gear ratio consists only of the pole number (2 in the
example).
Figure 9-10
7. Click "OK" to confirm.
This completes the configuration of the actual value acquisition. In the next step, configure
the safety function.
9.5.3

Configuring the control type and the SLS

Configuring the control type and the SLS
Now configure the control type and the SLS safety function.
1. Click "Control type / safety functions" below "Functions" in the secondary navigation.
2. Select "via PROFIsafe" as control type. Insert the PROFIsafe telegram later during the
safety commissioning.
Getting Started - SINAMICS Startdrive
Getting Started, 01/2015
Actual value acquisition pole pair number configuration extended functions
Safety Integrated
9.5 Commissioning extended functions
75