Delta RPI M30A_120 Operation And Installation Manual page 31

Grid-tie transformerless solar inverter
Table of Contents

Advertisement

CAUTION
Machine and equipment damage may occur.
- Make sure to choose proper size for AC cable.
- Failed to follow these instructions may cause AC plug damage.
- AC plug's installation must meets the local electrical code.
- If there is any conflict between installation instruction and electrical code,
please follow the electrical code.
Follow the steps below to strip the wires before assembling the AC plug:
• Remove 68.5 mm (MAX) of AC cable outer jacket.
• Trim the L1, L2, L3, and N wire to 70 mm (MAX).
• Strip 20 mm of insulation from all wires ends for RPI M30A.
5 * 20 mm
PE
N
L1
L2
L3
End sleeve is not able to be installed if 25mm²(4AWG) is applied.
16mm²(6AWG) Dimensions of the recommended sleeve are indicated in Fig.
WIRE SIZE
L
16mm²
28
6AWG
70 mm (MAX)
68.5 mm (MAX)
Figure 4-11 : Striping the wires
DIMENSIONS(mm)
F
18
F
L
W
B
Figure 4-12 : Cord end terminal
31
Outer Jacket
5.8
6.2
D
C
Wiring
8.7