Testing And Adjusting; Final Steps; Service Mode - BEA LZR-FLATSCAN REV-LZ User Manual

Safety sensor for revolving doors
Table of Contents

Advertisement

5

TESTING AND ADJUSTING

Check the correct positioning of the
safety fields by placing an object in
the detection field.
After changing the angle, the sensor position or the environment, always launch a teach-in and test the correct
positioning of the detection fields.
6

FINAL STEPS

«click»
Close the cover starting on the narrow
side (1). Do not hesitate to push.

SERVICE MODE

> 3 sec.
A
If necessary, adjust the tilt angle of the laser curtain by turning the
tilt angle adjustment screw (from 2° to 10°).
To open the sensor again, position a screwdriver in the
notch and pull upwards until the cover comes loose.
The service mode deactivates the safety detection during 15 minutes and can be
useful during an installation, a mechanical teach-in of the door or maintenance
work.
To enter the service mode, push on the button for at least 3 seconds.
When the sensor is in service mode, the LED is off.
To exit the service mode, push again for at least 3 seconds.
The service mode is deactivated automatically when launching a teach-in.
A
PZ1
B
«click»
B
9