Primary Number Event Codes - Honeywell NOTIFIER UDACT-2 Instruction Manual

Universal digital alarm communicator
Table of Contents

Advertisement

Primary Number Event Codes

Primary 24 Hour Test Time: Enter the start time (in HH:MM format, where HH = 00 to 23 hours, MM = 00 to 59 minutes) at which
the test should be performed and transmitted. The first test will be performed at that time, and again as indicated by the Test Time
Interval setting.
*Note: When using 4 + 2 Format, some receivers will display the character "A" as "0".
Secondary:
Secondary Format: Select SIA, 4+2 standard*, or Ademco Contact ID.
Secondary Phone Number: Enter the secondary phone number. The phone number may be preceded by one or more command
codes. See the description of the "Additional Phone Commands" field below.
Secondary Account Code: Enter the vendor account code for the secondary phone number. The field for 4+2 Standard and Ademco
Contact ID accommodates four digits. The field for SIA accommodates six digits.
Secondary Test Time Interval: Select 4, 6, 8, 12, or 24 for automatic test report transmission to the secondary phone number every
4, 6, 8, 12, or 24 hours.
NOTE: Test time intervals exceeding 6 hours do not comply with UL 864 10th Edition.
Secondary 24 Hour Test Time: Enter the time (in HH:MM format, where HH = 00 to 23 hours, MM = 00 to 59 minutes) at which
the test should be performed and transmitted. The first test will be performed at that time, and again as indicated by the Test Time
Interval setting.
*Note: When using 4 + 2 Format, some receivers will display the character "A" as "0".
SIA Device Address: This field appears if SIA has been selected as the format for either the primary or secondary phone number. Select
whether to have the device address appear in Central Station reporting or not by selecting "Enable" or "Disable".
Ademco Contact ID: These optional fields appear if Ademco Contact ID has been selected as the format for either the primary or second-
ary phone number. Entries in these fields will appear in the reporting at the Central Station.
• Group - enter a value of 1 through 99. The number entered will appear in the "GG" reporting field described in Section 5.2,
"Ademco Contact ID", on page 29.
• General Points Device Number - enter a value of 1 through 999. The number will appear in the "CCC" reporting field for general
reports. Refer to Section 5.2, "Ademco Contact ID", on page 29.
Additional Phone Commands:
The commands listed below may be added to the phone number. Multiple commands may be used.
• * - Phone Service Dependent - Functions as the * in the phone UDACT-2's phone system.
• # - Phone Service Dependent - Functions as the # in the phone UDACT-2's phone system.
• C - Look for secondary dial tone for up to 2 seconds (then, dial anyway).
• D - 3 second pause.
• E - 5 second pause.
3.3 Primary Number Event Codes
This screen displays the default Event Code assignments for the protocol selected for the primary telephone line. The Event Codes are
user-programmable.
Description: This display-only field gives a text description of the Event Code.
Setting: This field may be modified to accommodate the user. The field may be changed to an alpha code, numeric code, or alpha-
numeric code. SIA and "4+2" accomodate two digits, Ademco Contact ID accomodates three.
UDACT-2 — Instruction Manual P/N 54089:B3 10/29/2019
Figure 3.3 Primary Number Event Codes
Programming
25