Installation Options
Rear Mounting
BMP-1 Blank Module Plate
The UDACT-2 mounts on the back of a BMP-1 blank module plate, so it can be mounted on a DP-DISP, DP-DISP2, or ADP-4B dress
panel.
Step
Action
1
Disconnect AC power and disconnect batteries.
2
Mount the BMP-1 onto a DP-DISP, DP-DISP-2, or ADP-4B dress panel by placing it over the two threaded studs and
fastening with two 4-40 KEPS hex nuts (included with BMP-1) as indicated.
3
Attach four 3/16" hex standoffs (p/n 42170, included with UDACT-2) to the BMP-1's four threaded studs.
4
Align the UDACT-2 over the standoffs and fasten with four 4-40 screws (included with UDACT-2, p/n 38122).
Standoffs
Screws
Remote Installation
For remote installation, the UDACT-2 can mount in an ABS-8RB, UBS-1B, or UBS-1R enclosure. The unit must be placed within the
same room and within 20 feet (6.1 meters) of the panel or network annunciator. Wiring must be enclosed in conduit.
UDACT-2 — Instruction Manual P/N 54089:B3 10/29/2019
Screws
Screws
1
Front Mounting (two possible positions)
Figure 2.8 CHS-M3 Installation
Nuts
Figure 2.9 BMP-1 and Dress Panel Installation
Tab
Screws
2
Tab
Installation and Wiring
17