Section 2: Installation And Wiring; Installation Options - Honeywell NOTIFIER UDACT-2 Instruction Manual

Universal digital alarm communicator
Table of Contents

Advertisement

2.1 Installation Options

The UDACT-2 is either installed internally in the panel cabinet or remotely in an ABS-8RB, UBS-1B or UBS-1R enclosure. The follow-
ing table contains information specific to each panel that is compatible with the UDACT-2. See "Internal Installation" on page 13 for
instructions on internal installation and "Remote Installation" on page 17 for instructions on remote installation. Additional information
required for installing the UDACT-2 in a specific Fire Alarm Control Panel will be found in the appropriate appendix relating to that
panel.
Host Control Panel
AFP-200
AFP-300/AFP-400
AM2020/AFP1010
NCA-2
NCA
NFS2-640
NFS-320
NFS-320SYS
NFS-640
NFS2-3030
NFS-3030
Internal Installation
CAUTION:
!
REMOVE ALL POWER FROM THE CONTROL PANEL BY DISCONNECTING AC AND BATTERIES BEFORE
INSTALLATION OR MAKING ANY CONNECTIONS TO PREVENT PERSONAL AND/OR CIRCUIT DAMAGE.
Mounting on the NFS-320 Chassis
The UDACT-2 is installed on the chassis within the NFS-320 backbox as described and shown below:
Step
Action
1
Disconnect AC power and disconnect batteries.
2
Remove the KDM-R2 keypad. Do not remove the onboard power supply.
3
Remove the two 1" standoffs from the bottom of the CPU and replace with the two #4-40 x 0.5" standoffs provided with
the UDACT-2.
4
Position the UDACT-2 on the standoffs and fasten with two #4-40 x 0.25" screws provided.
Onboard
Power Supply
UDACT-2 — Instruction Manual P/N 54089:B3 10/29/2019

Section 2: Installation and Wiring

Host Panel Cabinet Style Remote Cabinet
AFP-200 Cabinet
CAB-400AA
CAB-3/4 Series
CAB-3/4 Series
CAB-3/4 Series
CAB-3/4 Series
CAB-3/4 Series
NFS-320 Cabinet
CAB-3/4 Series
CAB-3/4 Series
CAB-3/4 Series
CAB-3/4 Series
NFS-320
Chassis
UDACT-2
Figure 2.1 NFS-320 Chassis Installation
ABS-8RB, UBS-1B, UBS-1R
ABS-8RB, UBS-1B, UBS-1R
ABS-8RB, UBS-1B, UBS-1R
ABS-8RB, UBS-1B, UBS-1R
ABS-8RB, UBS-1B, UBS-1R
ABS-8RB, UBS-1B, UBS-1R
ABS-8RB, UBS-1, UBS-1B, UBS-1R
ABS-8RB, UBS-1, UBS-1B, UBS-1R
ABS-8RB, UBS-1B, UBS-1R
ABS-8RB, UBS-1B, UBS-1R
ABS-8RB, UBS-1B, UBS-1R
ABS-8RB,UBS-1B, UBS-1R
Table 2.1 Installation Options
Where Installed
Remote Only
Remote Only
Internal or Remote
Internal or Remote
Internal or Remote
Internal or Remote
Internal or Remote
Internal or Remote
Internal or Remote
Internal or Remote
Internal or Remote
Internal or Remote
screw and
standoff locations
13