Section 3: Programming; General Settings 1 - Honeywell NOTIFIER UDACT-2 Instruction Manual

Universal digital alarm communicator
Table of Contents

Advertisement

The UDACT-2 is programmed using VeriFire Tools, version 6.6 or higher.
NOTE: Only one UDACT-2 can be installed on a host's EIA-485 ACS circuit.
NOTE: Check the time on the laptop used for VeriFire Tools programming for accuracy. The 24 hour test time is determined
from the laptop's time signature taken from the downloaded VeriFire Tools database.

3.1 General Settings 1

Node ID: Select the node number of the UDACT-2's host panel.
Panel Type: Select the UDACT-2's host panel or network annunciator type. The NFS-320 menu selection includes the NFS-320SYS.
Reporting Type: Select from the following lists of reporting types.
• Disable Communications - Select this option to disable Central Station reporting.
• Zone Reporting, Receive Only - Select when the UDACT-2 will receive messages from the panel, but will not transmit back to
the panel. When "Receive Only" is selected, an external trouble relay must be used. Refer to Section 2.6 on page 20. This
selection should be made when an annunciator shares the same EIA-485 address as the UDACT-2.
• Zone Reporting, Receive/Transmit - Select when the UDACT-2 will receive messages from the panel, and will transmit a
response back to the panel. Typically this selection is made when a UDACT-2 does not share an EIA-485 address with another
device.
• Point Reporting, Receive Only - Select when the UDACT-2 will receive messages from the panel, but will not transmit back to
the panel. When "Receive Only" is selected, an external trouble relay must be used. Refer to Section 2.6 on page 20. This
selection should be made when an annunciator shares the same EIA-485 address as the UDACT-2.
• Point Reporting, Receive/Transmit - Select when the UDACT-2 will receive messages from the panel, and will transmit a
response back to the panel. Typically this selection is made when UDACT-2 does not share an EIA-485 address with another
device.
The AFP-200 panel does not accommodate Point Reporting.
AC Loss Reporting Delay: Select the time delay for AC Loss Reporting. Values are 1, 2, 6, 7, 8, 9, 10, 11, 15, 16, 17, 20, 21, 22 and 23
hours, and Immediate for immediate reporting. Refer to "Programming Features Subject to AHJ Approval" on page 7 for UL-compliant
values.
Backup Reporting: Select the type of backup reporting desired. Reports will be transmitted to the secondary phone number when
attempts to notify the primary phone number fail, or reports will always be transmitted to the secondary phone number.
Daylight Savings Time: Select Enabled or Disabled.
Daylight Savings Format: Select" Day of Week" or "Date"
• Day of Week - Select the starting and ending weeks, days, months and times. The start and stop times must be at least 24 hours
apart.
• Date - Select the specific starting and ending month and day. The day fields must be in different months.
ACS Addresses: Select a start and end address for addresses that will be monitored.
- The NFS2-3030, NFS-3030, NCA-2, NCA, AM2020 and AFP1010 use:
23

Section 3: Programming

NFS2-640
Figure 3.1 General Settings 1 Screen
UDACT-2 — Instruction Manual P/N 54089:B3 10/29/2019