C.5

Measured values for wire break diagnostic

Measured values on diagnostic event "wire break", dependent on diagnostics enables
Error events initiate a diagnostics entry and trigger a diagnostics interrupt if configured
accordingly.
Table C- 14
Measured values for wire break diagnostic
Format
Parameter assignment
S7
"Wire break" diagnostics enabled
"Overflow/Underflow" diagnostics
enabled or disabled
("Wire break" diagnostics takes priority
over "Overflow/Underflow" diagnostics)
"Wire break" diagnostics disabled
"Overflow/Underflow" diagnostics
enabled
"Wire break" diagnostics disabled
"Overflow/Underflow" diagnostics
disabled
Analog Input Module AI 8xU/I/R/RTD BA (6ES7531-7QF00-0AB0)
Manual, 03/2019, A5E44792324-AA
C.5 Measured values for wire break diagnostic
Measured values
Explanation
32767
7FFF
"Wire break" or "Open circuit" diagnostic
H
alarm
-32767
8000
H
-32767
8000
Measured value after leaving the undershoot
H
range
Representation of analog values
Measured value after leaving the under-
shoot range
Diagnostic alarm "Low limit violated"
59