Backup And Restore Using Prosave - Siemens SIMATIC KTP400 Basic Operating Instructions Manual

Hmi device
Hide thumbs Also See for SIMATIC KTP400 Basic:
Table of Contents

Advertisement

6.5.3

Backup and restore using ProSave

Requirements
● The HMI device is connected to a PC on which ProSave is installed.
● The data channel is parameterized on the HMI device.
Procedure – backup
Proceed as follows:
1. Go to the Windows Start menu and start ProSave on the PC.
2. Select the HMI device type in the "General" tab.
3. Select the type of interconnection for the HMI device and the PC.
Set the connection parameters.
4. Select the data to be backed up in the "Backup" tab.
– "Complete backup" generates a backup copy of configuration data, recipe data and
– "Recipes" generates a backup copy of the HMI device's recipe data records in PSB
– "Recipes (CSV format)" saves a backup copy of the HMI device's recipe data records
– "User management" generates a backup copy of the HMI device's user data in PSB
5. Select the folder and file name for the *.psb" backup file .
When generating a backup copy of recipes in CSV format, only select a folder. A CSV file
is generated for each recipe in this folder.
6. Set "Transfer" mode on the HMI device.
If automatic transfer mode is enabled on the HMI device, the HMI device automatically
sets "Transfer" mode when a backup is initiated.
7. Start the backup operation in ProSave with "Start Backup".
Follow the instructions in ProSave.
A progress bar opens to indicate the progress of the operation.
Result
The system outputs a message when the backup is completed.
A backup copy of the data is now available on the PC.
KTP400 Basic, KTP600 Basic, KTP1000 Basic, TP1500 Basic
Operating Instructions, 08/2008, A5E01075587-01
the HMI device image to a file in PSB format.
format.
to a text file in CSV format. The semicolon is used as column separator.
format.
Commissioning a project
6.5 Backup and restore
71