Mounting and connecting
3.3 Connecting the HMI device
Configuring the PC/PPI cable
Configure the transmission speed using the DIP switches of the PC/PPI cable if using the
PC/PPI cable to interconnect the HMI device with the configuration PC.
Note
Set a lower bit rate if the connection is lost during the operating system update. If you use a
higher bit rate, you must use the PC/PPI cable release 3 or higher. The version code is
printed on the cable (for example, "E-Stand 3" corresponds to version 3).
You can set the following bit rates:
Bit rate in kbps
115.2
57.6
38.4
19.2
9.6
4.8
2.4
1.2
36
DIP switch 1
DIP switch 2
1
1
0
0
0
0
1
1
KTP400 Basic, KTP600 Basic, KTP1000 Basic, TP1500 Basic
Set the DIP switches 1 to 3 to the same
value as in WinCC flexible. DIP switches
4 to 8 must be set to "0". In the figure,
the bit rate is set to 115.2 kbps.
DIP switch 3
1
1
0
0
1
1
0
0
Operating Instructions, 08/2008, A5E01075587-01
0
1
0
1
0
1
0
1