Timing And Settings; Diagnostic Flash Codes; Table 3 - Timings And Settings; Figure 4 - Flash Code Led - Rheem Guardian PowerVent Training Manual

Electronic spark to pilot gas (fvir) water heaters
Hide thumbs Also See for Guardian PowerVent:
Table of Contents

Advertisement

Guardian PowerVent Training Manual
T
A
S
IMING
ND
ETTINGS
Unless otherwise noted, all nominal functional timings are to be accurate to ± 1 second or 5%,
whichever is greater, over the specified operating temperature and voltage ranges
Temperature differentials (factory pre-set)
Temperature set point range
Flame Establishing Period
Flame Failure Response Time
Recycle Time
Lockout Time
Vacuum switch short cycle
Vacuum switch long cycle
Pre-purge time (factory pre-set)
Inter-purge Time
Post-purge Time (factory pre-set)
Ignition Activation Period
Trial for Ignition Period
Valve Sequence Period
Automatic Restart Time
Number of ignition trials
Table 3 – Timings and Settings
D
F
IAGNOSTIC
LASH
Another new feature of the Guardian PowerVent is the LED diagnostics system built into the
Figure 4 – Flash Code LED
A green LED is provided to indicate system status.
When a fault occurs within the water heater, the control will output a code using an LED.
Timing/ Setting
C
ODES
control module. When the unit faults, the LED will flash a
certain number of times. A flashing green LED diagnostic code
indicates that a sequence of events has forced a lockout
condition and is in a lockout state. Number of flashes indicates
the type of failure. The flash code or number of flashes will
occur followed by a pause before it repeats. Any power
interruption of more than 2 seconds – with the reapplication of
power, will re-set the controls. If a fault condition existed prior
to the reset, the fault condition will clear with the exception of
the FV sensor codes. If the fault condition still exists after the
application of power, the control will indicate the appropriate
fault.
SVC900; Rev 1
Nominal
15
0
0
95
- 158
2 Seconds
2 Seconds
15 Seconds
285 + pre-purge time in Seconds
9 Seconds
12 Seconds
15Seconds
30 Seconds
30 Seconds
75 Seconds
75 Seconds
225 Seconds
60 minutes
3 times / trails