Drain nipple
<SM800AT-E>
Waterproof rubber cap
• When there is a possibility of freezing of drain at the
cold district or a snowfall area, be careful for drainage
ability of drain. The drainage ability increases when a
knockout hole on the base plate is opened. (Open the
knockout hole to outside using a screwdriver, etc.)
Optional Installation Parts
(Local Procure)
Parts name

Refrigerant piping

A
Liquid side : Ø6.35 mm or Ø9.52 mm
Gas side : Ø12.7 mm or Ø15.9 mm
Pipe insulating material
B
(polyethylene foam, 6 mm thick)
C
Putty, PVC tapes
Waterproof rubber cap
Base plate
Knockout hole
Open
Drain nipple
Q'ty
Each one
Each one
Refrigerant Piping Connection
TAKE NOTICE THESE IMPORTANT
4 POINTS BELOW FOR PIPING WORK
1. Keep dust and moisture away from inside the
connecting pipes.
2. Tightly connect the connection between pipes
and the unit.
3. Evacuate the air in the connecting pipes using
VACUUM PUMP .
4. Check gas leak at connected points.
<Piping connection>
Capacity
rank
RAV-
diameter
SM560
SM800
For Reference
If a heating operation would be continuously performed
for a long time under the condition that the outdoor
temperature is 0°C or lower, draining of defrosted water
may be difficult due to freezing of the bottom plate,
resulting in a trouble of the cabinet or fan.
It is recommended to procure an anti-freeze heater
locally for a safety installation of the air conditioner.
For details, contact the dealer.
1
9
CAUTION
Liquid side
Outer
Outer
Thickness
diameter
Ø6.4
0.8
Ø12.7
Ø9.5
0.8
Ø15.9
Gas side
Thickness
0.8
1.0