Sizing table, flue system for cascade operation
Wolf FGB
appliance combination
28 + 28
28 + 35
35 + 35
28 + 28 + 28
28 + 28 + 28
28 + 28 + 35
28 + 28 + 35
28 + 35 + 35
28 + 35 + 35
35 + 35 + 35
35 + 35 + 35
28 + 28 + 28 + 28
28 + 28 + 28 + 28
28 + 28 + 28 + 28
28 + 28 + 28 + 35
28 + 28 + 28 + 35
28 + 28 + 28 + 35
28 + 28 + 28 + 35
28 + 28 + 35 + 35
28 + 28 + 35 + 35
28 + 28 + 35 + 35
28 + 28 + 35 + 35
28 + 35 + 35 + 35
28 + 35 + 35 + 35
28 + 35 + 35 + 35
28 + 35 + 35 + 35
35 + 35 + 35 + 35
35 + 35 + 35 + 35
35 + 35 + 35 + 35
35 + 35 + 35 + 35
* Max. height, shaft inlet to outlet point
82
31. Technical information, balanced flue
Connection pipe
DN110
DN110
DN110
DN110
DN110
DN110
DN110
DN110
DN110
DN110
DN110
DN110
DN110
DN110
DN110
DN110
DN110
DN110
DN110
DN110
DN110
DN110
DN110
DN110
DN110
DN110
DN110
DN110
DN110
DN110
Flue diameter
Header
DN110
DN110
DN110
DN110
DN110
DN110
DN110
DN110
DN110
DN110
DN110
DN110
DN110
DN125
DN110
DN110
DN125
DN125
DN110
DN110
DN125
DN125
DN110
DN110
DN125
DN125
DN110
DN110
DN125
DN125
Height, vertical*
Vertical
DN110
DN110
DN110
DN110
DN125
DN110
DN125
DN110
DN125
DN110
DN125
DN110
DN125
DN125
DN110
DN125
DN125
DN160
DN110
DN125
DN125
DN160
DN110
DN125
DN125
DN160
DN110
DN125
DN125
DN160
3064458_201811
in m
50
50
50
46
50
38
50
32
50
29
50
19
46
50
15
39
45
50
12
32
39
50
10
26
33
50
9
25
31
50

Hide quick links: