Parameter H51
DHW configuration
Factory setting: see table
Setting range: 1 to 4
Individual setting:_____
Parameter H52
Pasteurisation
Factory setting: see table
Setting range: 0 to 80
Individual setting:_____
Parameter H53
Activation interval
Pasteurisation
Factory setting: see table
Setting range: 1 to 7 days
Individual setting:_____
40
17. Parameter description
The DHW configuration is used to set the type of DHW heating..
If the configuration is modified, all parameters are returned to
factory settings (except H12 and H40).
1
Combi mode
Configuration
2
Combi mode + solar integration
Configuration
3
Cylinder operation
Configuration
4
No DHW (heating mode only)
Configuration
Configuration 1
Configuration 3
Parameter H52 is only visible during DHW configuration in cylinder mode.
If the appliance is connected to a BM-2, pasteurisation mode is disabled.
The BM-2 takes over this function.
If pasteurisation is enabled (setting > 0), the DHW cylinder is heated to the
temperature set here, unless the cylinder temperature has already reached
the pasteurisation temperature within the activation intervals (H53).
Pasteurisation is disabled with the value 0.
If pasteurisation was enabled in H52, the interval for activation of this function
can be specified.
If the appliance is connected to a BM-2, the pasteurisation mode activation
interval is disabled. The BM-2 takes over this function.
If set to 5, pasteurisation takes place every 5 days.