Wolf FGB-K Series Installation And Maintenance Instructions For Contractors page 39

Wall mounted gas condensing/combi boiler
Hide thumbs Also See for FGB-K Series:
Table of Contents

Advertisement

System configuration 02
Direct heating circuit and one or more circuits with mixer via
mixer modules
(no direct heating circuit at the condensing boiler)
• Burner starts subject to demand from the connected
circuits with mixer
• Internal appliance pump is enabled as a feed pump
• Thermostatic boiler control;
set value is specified by circuits with mixer
System configuration 60
Cascade (automatic setting if cascade
module is connected)
• eBus address H10 must be set for each
condensing boiler
• Burner starts following a demand from the cascade
module via eBus
(0-100 % burner output; min. to max. within the
programmed limits H02 and H04)
• Internal appliance pump is enabled as a feed pump
• Header temperature control via cascade module
• Automatic output reduction when approaching TV
is enabled. Shutdown when TV
• A low loss header or plate heat exchanger can be used to
provide hydraulic separation.
In these schematic diagrams, shut-off valves, air vent valves and safety equipment are not fully represented.
These should be provided subject to the individual system, in line with the applicable standards and regulations.
Hydraulic and electrical data can be found in the Hydraulic System Solutions technical guide.
Parameter H41
Feed/heating circuit pump speed,
DHW
Factory setting: see table
Setting range: 15 to 100 %
Individual setting:_____
3064458_201811
17. Parameter description
(H08)
max
is reached
max
Important information:
In DHW mode, the pump runs at this set value. Independent of the pump control type
set in H37.
HK
eBus
H10 = 1
H10 = 2
MK1
M
KM
SAF
39