Wolf FGB-K Series Installation And Maintenance Instructions For Contractors page 45

Wall mounted gas condensing/combi boiler
Hide thumbs Also See for FGB-K Series:
Table of Contents

Advertisement

Commissioning
Top-up water
Example:
3064458_201811
18. Filling the heating system / trap
Vent the system completely at the maximum system temperature.
The commissioning parameters must be recorded in the system log. This system log
must be handed to the system operator following commissioning of the system. From
that point onward, the operator is responsible for maintaining and keeping the system
log. The system log is provided with the accompanying documents.
The water values, in particular the pH value, electrical conductivity and hardness,
must be measured annually and documented in the system log.
The total amount of fill water used over the life cycle of the boiler must not exceed
three times the system volume (oxygenation!). Where a system requires large
volumes of top-up water (e.g. more than 10 % of the system volume per year), the
cause must be sought immediately and the fault remedied.
Limits in relation to specific system volume V
(V
= system volume / max. rated heating output
A
Total hardness conversion: 1 mol/m³ = 5.6 °dH = 10°fH
V
≤ 20 l/kW
A
Total hardness /
total alkaline earths
[kW]
[°dH]
[mol/m³] LF [µS/cm] [°dH]
1
≤ 50
≤ 16.8
≤ 3.0
2 50-200 ≤ 11.2
≤ 2
3 200-600 ≤ 8.4
≤ 1.5
4 ≤ 600
≤ 0.11
≤ 0.02
3)
The total amount of fill and top-up water over the life cycle of the boiler must not exceed three times the nominal volume of the
heating system.
According to VDI 2035, in systems with multiple boilers, use the maximum rated heating output of the smallest heat source
1)
2)
High salinity < 800 µS/cm
Low salinity < 100 µS/cm
< 0.11°dH recommended standard; permissible up to a limit of < 1 °dH
3)
System with an FGB-28 system volume = 800 l
Total hardness of untreated potable water = 18°dH
V
= 800 l / 28 kW = 29 l / kW
A
Because the specific system volume V
of < 50 kW, the fill and top-up water must be in the range of 2 to 11.2°dH If the total
hardness of the untreated potable water is too high, some of the filling and top-up
water must be desalinated.
A% desalinated water must be added.
A = 100% - [(C
-0.1°dH) / C
max
C
:
Maximum permissible total hardness in °dH
max
C
:
Total hardness of untreated potable water in °dH
potable water
A = 100% - [(11.2°dH - 0.1°dH) / (18°dH - 0.1°dH)] x 100% = 38%
38% of the filling and top-up water must be desalinated.
V
= 38% x 800 l = 304 l
treatment
At least 304 L of desalinated water must be added when filling the system.
The system can then be topped up with potable water.
V
> 20 l/kW and < 50 l/kW
A
Conductiv-
Conductiv-
Total hardness /
ity
2)
total alkaline earths
at 25°C
[mol/m³] LF [µS/cm] [°dH]
< 800
≤ 11.2
≤ 2
≤ 8.4
≤ 1.5
< 100
≤ 0.11
≤ 0.02
3)
≤ 0.11
≤ 0.02
3)
is between 20 and 50 l/kW with a total output
A
- 0.1°dH)] x 100%
potable water
A
)
1)
V
≥ 50 l/kW
A
Conductiv-
Total hardness /
ity
2)
total alkaline earths
at 25°C
at 25°C
[mol/m³]
LF [µS/cm]
< 800
≤ 0.11
≤ 0.02
< 800
3)
≤ 0.11
3)
≤ 0.02
< 100
≤ 0.11
≤ 0.02
< 100
3)
≤ 0.11
≤ 0.02
3)
ity
2)
45

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Fgb seriesFgb-28Fgb-k-35Fgb-35Fgb-k-28

Table of Contents