Samson TROVIS 5757-3 Mounting And Operating Instructions page 29

With process controller for domestic hot water heating
Hide thumbs Also See for TROVIS 5757-3:
Table of Contents

Advertisement

F
Function
16 Function of switching
output
17 Pump protection
Firmware version 2.20 and higher
1)
Parameter list
The parameters have the setting ranges as listed below.
P = Parameter
P
Parameters
01
Set point W1
02
Set point W2
03
Lower measuring range value Xmin
04
Upper measuring range value Xmax
05
Upper limit (GWH)
06
Lower limit (GWL)
07
Proportional-action coefficient K
08
Reset time Tn
09
Derivative-action time Tv
10
Actuator transit time Ty
11
Set-back difference
12
Heating period to maintain heat exchanger at
constant temperature
Firmware version 2.20 and higher
1)
EB 5757 EN
WE
Meaning
3
1: Not active
2: Fault alarm
3: Circulation pump (DHW)
4: Circulation pump (heating)
5: Tapping
6: Circulation pump (heating) reversed
1
0: Passive
1)
1: Active
WE = Default setting
P
1)
1)
WE
Adjustment range
60 °C
0 to 100 °C
70 °C
0 to 100 °C
0 °C
–50 to 90 °C
100 °C
10 to 150 °C
95 °C
0 to 100 °C
5 °C
0.8
15 s
0 s
25 s
8 K
24.0 h
Appendix
0 to 20 °C
0.1 to 50
0 to 999 s
0 to 999 s
0 to 240 s
0 to 30 K
0 to 25.5 h
29