Technical Data
Supply Voltage – Direct Voltage (DC)
Permitted ripple of the input voltage
Maximum inrush current at ≤ 110 V
Maximum inrush current at 220 V to 300 V
Supply Voltage – Alternating Voltage (AC)
Permitted harmonics
Maximum inrush current at ≤ 115 V
Maximum inrush current at 230 V
Environmental Conditions (operate the unit in a dry room only!)
Temperature Data
Recommended operating temperature
Temperature during transport and storage
Air humidity data
Mean relative humidity per year
Maximum relative humidity
Condensation during operation
Condensation during transport and storage
Other environmental information
Max. altitude above sea level
pollution degree
Protection degree according IEC 60529
overvoltage category
Fuse
Internal fuse, not replaceable
2
Find more on the technical data in the corresponding manuals.
Unrestricted Product Information
C53000-X1150-C601-2,
15 %
< 15 A
≤ 22 A; after 250 µs: < 5 A
2 kHz
< 15 A
≤ 22 A; after 250 µs: < 5 A
-5 °C to +55 °C (23 °F to 131 °F)
-25 °C to +70 °C (-13 °F to 158 °F)
≤ 75 %
95 % 30 days a year
Not permitted
Permitted
2000 m
2
IP 20
III
2.0 A slow blow (not exchangeable)
T1.6A / 250V acc. to IEC 60127