Hide thumbs Also See for Touchpoint Plus:
Table of Contents

Advertisement

2) Slide the cover off carefully and place it on a clean, anti-static surface.
3) Fit the Modbus PCB by carefully aligning the connectors and pushing down gently, observing the orientation
shown below:
4) Connect the Modbus cables as shown below. (You should connect a 120Ω termination resistor (R
B to prevent reflections on the RS485 circuit if TPPL is the last node in a Modbus system highway.)
Note: External R
Some manufacturers have been known to incorrectly reverse their RS485 Data terminals, which can cause
MAN0984_Iss 4_01/19
Pt. No. 3011M5001
Electrical Power Connection and Interfacing
Modbus
Motherboard Showing the Modbus PCB Location
is not needed if the logic solver side has an internal R
T
Tx/Rx to fail. If this happens, simply swap over A and B cables and re-test.
MODBUS RTU
Label
Drain
D
Data +
A (D+)
Data -
B (D-)
Touchpoint
Plus
MODBUS RTU
Modbus RTU Connections
PCB
Modbus RTU
Terminals
CAUTION
Terminal ID
1
2
3
Touchpoint
Logic Solver
Plus
MODBUS RTU
48
B↔
Logic
A↔
Solver
D↔
Ethernet
Connector
) between A and
T
.
T
Logic Solver
D
A (D+)
B (D-)
Technical Handbook