Parameter Name
Span Calibration Gas Span Calibration Gas name string
Channel Enable
Channel Enable/Disable
Channel Number
Number
Channel Tag
25 characters
Normal State
Energized/De-Energised
Alarm Update
If enabled, only unacknowledged alarm
Function
conditions will be
considered during C&E evaluation for this
output channel.
An alarm acknowledgement will reset a
relay output that
is configured for alarm update function.
However if the alarm update is NOT enabled
the relay
contact will only be reset if the alarm is
reset.
Activate Delay Time
Delay time to activate the relay
Relay Hold Time
Delay time to de-activate the relay
MAN0984_Iss 4_01/19
Pt. No. 3011M5001
Parameter
Description
Configurable Parameter Reference Guide
Applies
Read/
Range
to
Write
Alphanumeric
mV Input
R/W
Character
Range
Relay
R/W
Disable/Enable
Output
Relay
R
1~48
Output
Alphanumeric
Relay
R/W
Character
Output
Range
Relay
Energized
R/W
Output
/De-Energised
Relay
R/W
Enable/Disable
Output
Relay
Output
R/W
0~3000
Relay
Output
R/W
0~3000
142
Default Value
Remark
If custom is selected gas as
target calibration gas, the
span calibration gas name
16 chars
can be edited. Otherwise it
should come from selected
sensor catalogue.
Disable
An unique number
(Auto assigning 1~16 LED )
-
Channel ID will be
automatically assigned
50 chars
Energized
Disable
0 sec
0 sec
Technical Handbook