Afc Status Codes (Green Led); Afc Fault Codes (Red Led); Unit Led (Blue Led) - Trane 7 Series Field Reference Data

Hyperion tam7, air handlers 2-5 ton, for use with bayev or bayw series heaters only
Hide thumbs Also See for 7 Series:
Table of Contents

Advertisement

AFC STATUS CODES (GREEN LED)

AFC STATUS LED
Description
ON SOLID
Power up and during last 4 fault history sequence
1 Flash (per second)
Stand-by or idle
Multiple Flash
CFM demand - 1 flash per 100 cfm

AFC FAULT CODES (RED LED)

AFC Fault
LED
OFF
No Fault
Solid On
Internal control failure
1
24VAC fuse blown
PM Data Corrupt or Missing / Motor Mismatch
2
4
Blower communication error (Status LED will be ON solid)
Internal communication error (refer to Unit LED on EVC, EHC, HHC)
5
EVC has detected a fault condition (refer to Fault LED on EVC)
11
EHC / HHC has detected a fault condition (refer to Fault LED on EHC / HHC)
12
(1) If Unit LED on AFC is flashing 2 times/second, AFC is causing the error.
NOTES:
(2) Unit LED on suspect control will flash 2 times/second on the suspect control.
All LED's will be off if power is not applied.

UNIT LED (BLUE LED)

Unit LED
1 Flash
Normal (1 flash every 4 seconds)
Rapid
Communication Busy Error (2 flashes per second)
Communications cannot be established with the AFC
SOLID ON
Off
No Power
Description
Description
TAM7­20
J1
STATUS
LED
UNIT
STATUS
STATUS
LED
W2
W2
UNIT
UNIT
R66
Q8
FAULT
FAULT
FAULT
LED
D28
R80
(1)(2)
TRANE U.S. INC.
HUM
T1
T2
J8
R7
BAR CODE
D5
C17
C16
D11
D10
1
R26
R28
R27
R16
D12
D30
C45
C44
D31
J9
Y1
R84
R38
R85
R82
O
D15
D18
C27
C26
D16
B
Yo
R45
R49
R55
R50
D20
R69
C32
C33
D21
R
R63
R56
R62
R74
Yo Jumper
DH Jumper
W1
W1
D33
C52
R101
R94
K2
R70
R100
D32
R73
J6

Hide quick links:

Advertisement

Table of Contents
loading

Table of Contents