Dip Switch S2

• Set the S2-1 and S2-2 dip switches for the Cooling
and Heating CFM/Ton.
INDOOR MODEL
S2‐1
OFF
OFF
*AM7A0A24H21SA
ON
ON
OFF
OFF
*AM7A0B30H21SA
ON
ON
OFF
OFF
*AM7A0C36H31SA
ON
ON
OFF
OFF
*AM7A0C42H31SA
ON
ON
OFF
OFF
*AM7A0C48H41SA
ON
ON
OFF
OFF
*AM7A0C60H51SA
ON
ON
* May be "A" or "T"
• Set the S2-3 and S2-4 dip switches for the Blower
Off Delay.
BLOWER OFF DELAY
1.5m @ 100%
NO DELAY
3m @ 50%
ENHANCED

Indoor Blower Timing

This ENHANCED MODE selection provides a ramping
up and ramping down of the blower speed to provide im-
proved comfort, quietness, and potential energy savings.
The graph on the right shows the ramping process.
Enhanced Mode works in cooling, HP, heating, Torque,
and constant CFM modes.
• Set the S2-5 dip switch for the airflow mode.
AIRFLOW MODE
*TORQUE
CONSTANT CFM
COOLING 
HEATING 
CFM/TON
CFM/TON
S2‐2
OFF
400
430
ON
360
390
OFF
380
410
ON
420
450
OFF
400
430
ON
360
390
OFF
380
410
ON
420
450
OFF
370
420
ON
350
400
OFF
390
440
ON
410
450
OFF
370
400
ON
330
360
OFF
350
380
ON
390
420
OFF
350
400
ON
330
380
OFF
370
420
ON
390
440
OFF
370
400
ON
380
410
OFF
390
420
ON
400
430
S2‐3
S2‐4
OFF
OFF
OFF
ON
ON 
OFF
ON 
ON
S2‐5
OFF
ON
OUTDOOR
OUTDOOR
HP
1
1
R4
1
R NET 2
R1
U1
R13
R14

Airflow Control (AFC)

80%
Dehumidify
50%
Fast Coil Cooling
OFF
1
7.5
minute
minutes
COMPRESSOR OPERATION ON
* Torque mode is optional and is recommended for high static
applications. High static conditions dramatically increase energy
consumption with variable speed motors. Evaluate the blower
performance table in relationship to the duct system to determine
the benefit of each installation.
* For the 2 ton air handler, torque mode will reduce airflow when
static is above approximately 0.3" water column.
* For the 2-1/2, 3, and 3-1/2 ton air handlers, torque mode will
reduce airflow when static is above approximately 0.35" water
column.
* For the 4 and 5 ton air handlers, torque mode will reduce airflow
when static is above approximately 0.4" water column.
When selected, Torque Mode is used for cooling operation only.
All heating modes default to constant CFM.
TAM7­9
on
}
Capacity (Tons)
AC (System)
2 (Stages)
2 (Compressor)
S1
INDOOR
R NET 1
on
CFM/Ton
Cool Off Delay
Torque
D9
S2
C10
+12V
R22
S2
100% if necessary
Efficiency
as required
3
minutes
OFF
CFM
50%
OFF