Electric Wiring - Daikin VAM150FC Installation Manual

Total heat exchanger hrv (heat reclaim ventilation) (ceiling mounted duct type)
Hide thumbs Also See for VAM150FC:

Advertisement

E
LECTRIC WIRING
Before obtaining access to terminal devices, all power
supply circuits must be interrupted.
Connection of wiring
I
Connect the wires in accordance with the diagram of each
system.
I
All wiring must be performed by an authorized electrician.
I
All field supplied parts and materials and electric works must
conform to local codes.
I
Use copper wire only
Connection of wiring
I
A main switch or other means of disconnection, having a contact
separation in all poles, must be incorporated in the fixed wiring
in accordance with applicable legislation.
Do not turn on the main switch until all the wiring is complete.
I
A single switch can be used to supply power to units on the
same system. However, branch switches and branch circuit
breakers must be selected carefully.
I
Fit the power supply wiring of each unit with a switch and fuse as
shown in the drawing.
I
Be sure to give the electric grounding (earth) connection.
Complete system example
VRV
3
4
VRV
2
5
VRV
2
5
Power supply wiring
Transmission wiring
Switch
Fuse
1
Outdoor unit
2
Indoor unit
3
Power supply
4
Main switch
5
Remote controller
VAM150+250FC
Total Heat Exchanger
HRV (Heat Reclaim Ventilation)
4P586307-1 – 2019.06
1
Component electrical specifications
VAM
Units
Type
50 Hz
60 Hz
(*)
Power supply
MCA
MFA
(*)
Fan motor
KW
FLA
(*) MCA: Min. Circuit Amps
MFA: Max. Fuse Amps
KW:
Motor Rated Output
FLA: Full Load Amps
NOTE
For details, refer to ELECTRICAL DATA.
Specifications for field supplied fuses and wire
VAM
Type
Power supply wiring
Field supplied fuses
Wire
Size
Transmission wiring
Wire
Size
Precautions
1
Do not connect wires of different gauge to the same power
supply terminal. Looseness in the connection may cause
overheating.
When connecting more than one wire to the power supply
wiring, use a 2 mm
Same gauge wires
HRV
2
Keep total current of crossover wiring between indoor units less
than 12 A.
When using two power wiring of a gauge greater than 2 mm
(Ø1.6), branch the line outside the terminal board of the unit in
accordance with electrical equipment standards.
The branch must be sheathed so as to provide an equal or
greater degree of insulation as the power supply wiring itself.
HRV
3
Do not connect wires of different gauge to the same grounding
terminal. Looseness in the connection may deteriorate
protection.
4
Keep the power supply wiring distant from other wires to prevent
noise.
5
For remote controller wiring, refer to the "Installation manual of
the remote controller".
150F
JVE, 5VE
Power supply Max. 264 V/Min. 198 V
Power supply Max. 242 V/Min. 198 V
0.9
(A)
16
(A)
0.03x2
(kW)
0.4x2
(A)
150F
JVE, 5VE
16 A
H05VV-U3G
Wire size must comply with local codes
Shield wire (2 wire)
0.75-1.25 mm
2
(Ø1.6) gauge wire.
Different gauge wires
250F
0.9
16
0.03x2
0.4x2
250F
2
2
Installation manual
6