Field Wiring: Overview - Daikin LRYEN-AY1 Installation And Operation Manual

Co₂ conveni-pack outdoor unit and capacity up unit
Table of Contents

Advertisement

14 Electrical installation
14.2

Field wiring: Overview

a
X2M
X1M (A1P)
X3M
X1M
PE
X1M
PE
X2M
L1 L2 L3 N
C C1 W1 R P1 P2
c1
c2
d1 d2
3N~ 50 Hz
380-415 V AC
d
i
X1M
i
X1M
220-240 V AC
a
Capacity up unit (LRNUN5A7Y1)
b
Outdoor unit (LRYEN10A7Y1)
c1
Overcurrent fuse (field supply)
c2
Earth leakage circuit breaker (field supply)
d
Alarm panel (field supply) for:
d1: Caution output signal
d2: Warning output signal
e
Control panel (field supply) for operation output signal
f
Remote operation switch (field supply)
g
Remote low noise switch (field supply)
OFF: normal mode
ON: low noise mode
h
Operation output signal to expansion valves of all:
h1: Blower coils (field supply)
h2: Showcases (field supply)
Installation and operation manual
26
X3M
X1M (A1P)
TO
TO
TO
1
2
3
IN/D UNIT
OUT/D UNIT
MULTI UNIT
F1
F2
F1
F2 Q1 Q2
f
g
e
L N
P1 P2 F1 F2 T1 T2
L N
P1 P2 F1 F2 T1 T2
k
j
c1
P1 P2
c2
1N~ 50 Hz
INFORMATION
Indoor units (air conditioning). This field wiring overview
shows only one possible wiring for the indoor units (air
conditioning). For more possibilities, see the indoor unit
manual.
b
X4M
X1M (A1P)
X5M
X1M
PE
X1M (A1P)
TO
TO
TO
C C1 W1 R P1 P2
IN/D UNIT
OUT/D UNIT
MULTI UNIT
F1
F2
F1
F2 Q1 Q2
DIII
d1 d2
d
X2M
X2M
k1
k2
k3
k4
k5
i
Indoor unit (air conditioning)
j
User interface for indoor units (air conditioning)
k
Safety system (field supply). Example:
k1: Control panel
k2: CO
2
k3: Safety alarm (lamp)
k4: Ventilation (natural or mechanical)
k5: Shut off valve
l
Communication box (BRR9B1V1)
m
Monitoring system (field supply)
Wiring:
RS-485
RS-485 transmission wiring (mind polarity)
DIII
DIII transmission wiring (no polarity)
R1
Operation output
X4M
X5M
1
2
3
L1 L2 L3 N
f
g
3N~ 50 Hz
380-415 V AC
e
h
h1
h2
R1
l
X1M
X3M
PE
X3M
X1M PE
A+ B- F1 F2
L N
m
c1
c2
1N~ 50 Hz
220-240 V AC
refrigerant leak detector
LRYEN10A7Y1+LRNUN5A7Y1
CO₂ Conveni-Pack outdoor unit and capacity up unit
4P605461-1B – 2020.08
X1M
PE
c1
c2

Advertisement

Table of Contents
loading

This manual is also suitable for:

Lrnun-ay1Lryen10a7y1Lrnun5a7y1

Table of Contents