Table A-1 shows the available wall power cord options for the PDU and iPDU features, which
must be ordered separately.
Table A-1 Wall power cord options for the PDU and iPDU features
Feature
Wall plug
code
6653
IEC 309,
3P+N+G, 16A
6489
IEC309
3P+N+G, 32A
6654
NEMA L6-30
6655
RS 3750DP
(watertight)
6656
IEC 309,
P+N+G, 32A
6657
PDL
6658
Korean plug
6492
IEC 309, 2P+G,
60A
6491
IEC 309, P+N+G,
63A
Notes: Ensure that the correct power cord feature is configured to support the power that
is being supplied. Based on the power cord that is used, the PDU can supply 4.8 - 19.2
kVA. The power of all of the drawers that are plugged into the PDU must not exceed the
power cord limitation.
The Universal PDUs are compatible with previous models.
To better enable electrical redundancy, each server has two power supplies that must be
connected to separate PDUs, which are not included in the base order.
For maximum availability, a preferred approach is to connect power cords from the same
system to two separate PDUs in the rack, and to connect each PDU to independent power
sources.
For detailed power requirements and power cord details about the 7014 racks, see the
"Planning for power" section in the IBM Power Systems Hardware IBM Knowledge Center
website:
http://www.ibm.com/support/knowledgecenter/api/redirect/powersys/v3r1m5/topic/p7ha
d/p7hadrpower.htm
For detailed power requirements and power cord details about the 7965-94Y rack, see the
"Planning for power" section in the IBM Power Systems Hardware IBM Knowledge Center
website:
http://www.ibm.com/support/knowledgecenter/api/redirect/powersys/v3r1m5/topic/p7ha
d/p7hadkickoff795394x.htm
Rated voltage
Phase
(Vac)
230
3
230
3
200 - 208, 240
1
200 - 208, 240
1
230
1
230 - 240
1
220
1
200 - 208, 240
1
230
1
Rated amperage
Geography
16 amps/phase
Internationally available
32 amps/phase
EMEA
24 amps
US, Canada, LA, and Japan
24 amps
US, Canada, LA, and Japan
24 amps
EMEA
32 amps
Australia and New Zealand
30 amps
North and South Korea
48 amps
US, Canada, LA, and Japan
63 amps
EMEA
Appendix A. Server racks and energy management