Storage management
6.4 Storage attributes
Creating attributes
To create an attribute, follow these steps:
1. Select the "Storage attributes" group in the navigation area of the APF engineering tool.
2. Specify the number of material lots permitted per storage location.
If this setting is subsequently modified, the corresponding function blocks must be created
again.
3. Click on the last row in the working area and specify the following properties:
4. Click the "Save" button.
82
Column
Pos
Name
UoM
Format
Enum_Mat
Low limit
High limit
TXTLIB
FCT_IO_BLOCK_NAME
Visible
Overview
Width
Position in the visualization order
Name of the attribute
Unit of the attribute
Format of the attribute
Name/coding of an enumeration
The "ENUM_MAT" field can only be selected if you have set "ENU‐
MERATION" or "Material" as the format of the attribute. You can cre‐
ate enumerations in SIMATIC Manager under "Global Declarations".
Lower operator control limit for numerical values
Upper operator control limit for numerical values
ID for multilingual management in the text library (non-editable; as‐
signed automatically)
Name of the output in the AS function block
You can use the "Visible" check box to specify whether the attribute
is displayed in the process picture.
Position of column in the "FB_STOR" overview picture
Width of column in the "FB_STOR" overview picture in pixels