Siemens SIMATIC PCS 7 System Manual page 132

Process control system, advanced process functions, engineering manual
Hide thumbs Also See for SIMATIC PCS 7:
Table of Contents

Advertisement

Diagnostics guide
10.1 Troubleshooting procedure
This means there are two types of archives. They are listed in the table below:
FB_MATCLASS
FB_MATTYPE_xxx
FB_MATATTRIB_xxx
FB_MATERIAL_xxx
FB_MATATTRIB_LOT
FB_MATERIAL_LOT
FB_STORGROUP
FB_STORATTRIB
FB_STORVALUE
FB_STORAGE
FB_PARAMGROUP
FB_PARAMATTRRIB_xxx
FB_PARAM_xxx
FB_PARAM_CALC_xxx
FB_ARCHGROUP
FB_ARCHVALUE_xxx
FB_ARCHIVING_xxx
FB_PROCEDURES
FB_STOR_ST_STATUS
FB_STOR_MAT_STATUS
To summarize:
● Runtime archives are written during runtime.
● Configuration archives are written during the engineering phase on the ES.
To avoid the loss of runtime archives, their content is not copied with server downloads. Archive
content is only copied the first time a server is downloaded (no existing OS folder in the target
location). This may mean that subsequent changes to archives during the engineering phase
are not applied to the server upon download.
Remedy:
1. If existing runtime databases can be overwritten in the engineering phase and no APF
runtime archives have yet been filled: Delete target folder and download entire server /
servers.
2. Export user archive content on the ES and import content on the server.
132
Archive name
Type
Configuration
List of all material classes
Configuration
List of material types of material class xxx
Configuration
Structure of material class xxx
Runtime
Storage location for materials of material
class xxx
Configuration
Structure of the material lot table
Runtime
Storage location for material lots
Configuration
List of all storage location groups
Configuration
Structure of the storage attributes
Configuration
Structure of the storage values
Runtime
Storage for storage locations
Configuration
List of all parameter set groups
Configuration
Structure of parameter set group xxx
Runtime
Storage location for parameter sets of the
parameter set group xxx
Runtime
Storage location for recalculations of pa‐
rameter sets of parameter set group xxx
Configuration
List of all archiving groups
Configuration
Structure of archiving group xxx
Runtime
Storage location for archiving data records
of archiving group xxx
Configuration
Storage location for procedures
Configuration
Storage location for storage location status
Configuration
Storage location for material status
Advanced Process Functions Engineering Manual
Explanation
System Manual, 07/2016, A5E38719921-AA