Table Of Standard Configurations - Studer Xtender XTH 5000-24 Installation And Operating Instructions Manual

Unit combining inverter, battery charger and transfer system
Hide thumbs Also See for Xtender XTH 5000-24:
Table of Contents

Advertisement

STUDER Innotec

17 Table of standard configurations

No. of
Denomination / description
config.
1107 Maximum current of the AC source
1108 Undervoltage of the empty battery
1109 Sub-voltage of the charged battery
1110 Restart voltage of the inverter after undervoltage of the battery
1111 Automatic startup at power up
1112 Inverter frequency
1121 Maximum DC voltage for stopping the Xtender
1126 Source assistance (Smart Boost) permitted
1138 Battery charge current
1139 Battery voltage correction according to the temperature
1140 Battery maintenance voltage
1143 Voltage 1 to allow a new battery cycle
1144 Duration of under voltage 1 to allow a new cycle
1145 Voltage 2 to allow a new battery cycle
1146 Duration of under voltage 2 to allow a new cycle
1156 Battery absorption voltage
1157 Duration of absorption
1159 Current at end of absorption
1161 Minimum interval between absorptions
1187 Sensitivity of the charge detection (100% approx.25W)
1189 Time interval between load search pulses
1190 Duration of undervoltage of battery before disconnection
1191 Dynamic compensation for undervoltage
1194 Battery adaptive low voltage allowed
1195 Max voltage for adaptive low voltage
1198 Time elapsing before transfer relay opens
1199 ACin voltage causing the opening of the transfer relay
1200 Immediate open critical threshold for the transfer
1246 Auxiliary contact 1 activated by voltage 1 {1247} after delays
{1248}
1247 Voltage 1under which auxiliary contact 1 is activated
1248 Delays on voltage 1 to activate auxiliary contact 1
1249 Auxiliary contact 1 activated by voltage 2 {1250} after delays
{1251}
1250 Voltage 2 under which auxiliary contact 1 is activated
1251 Delays on voltage 2 to activate auxiliary contact 1
1252 Auxiliary contact 1 activated by voltage 3 {1253} after delays
{1254}
1253 Voltage 3 under which auxiliary contact 1 is activated
1254 Delays on voltage 3 to activate auxiliary contact 1
1255 Voltage 1above which auxiliary contact 1 is deactivated after delays V/cell
1256 Delays on voltage {1255} to deactivate auxiliary contact 1
1258 Auxiliary contact 1 activated by power 1
1259 Power 1 above which auxiliary contact 1 is activated after delays
1260 Duration of power 1 for activating auxiliary contact 1
1261 Auxiliary contact 1 activated by power 2
1262 Power 2 above which auxiliary contact 1 is activated after delays
1263 Duration of power 2 for activating auxiliary contact 1
1264 Auxiliary contact 1 activated by power 3
1286 Output voltage
Installation and operating Instructions
Xtender V1.3
Xtender
Units
Fact.
Mod.
value
value
A
30
V/cell
1.93
V/cell
1.75
V/cell
2
y/n
no
Hz
50
V/cell
2.84
y/n
no
A
60
mV/°C/
-5
cell
V/cell
2.27
V/cell
2.1
min.
30
V/cell
1.93
sec.
180
V/cell
2.4
h
2
Adc
10
h
3
%
10
sec.
0.8
min.
3
y/n
yes
o/n
non
V/cell
2.08
sec.
8
Vac
180
Vac
50
y/n
yes
V/cell
1.95
min.
1
y/n
yes
V/cell
2
min.
10
y/n
yes
V/cell
2.05
min.
60
2.25
min.
60
y/n
yes
%
120
min.
1
y/n
yes
%
80
min.
5
y/n
no
Vac
230