Figure Element's (Ac Part) - Studer Xtender XTH 5000-24 Installation And Operating Instructions Manual

Unit combining inverter, battery charger and transfer system
Hide thumbs Also See for Xtender XTH 5000-24:
Table of Contents

Advertisement

STUDER Innotec

13 Figure element's (AC part)

Elem. Description
A
Input supply cable
B
Output
supply
cable
C
Connection of the
neutrals
D
Differential circuit
breaker
E
Earth-neutral
connection bridge
F
AC
output
protection devices
for the Xtender
G
Generator
H
Protection devices
at
the
Xtender
input
J
K
Connection plug /
socket
L
P
R
S
Secured grid
Installation and operating Instructions
Comment
The section is determined by means of the maximum current at
source and the protection device (H). In multi-unit systems, cables (A)
of the same phase must have the same length and section (see
comment fig. 12-2/3).
In multi-unit systems, cables (B) of the same phase must have the
same length and section (see comment fig. 12-2/3). The section must
be selected by means of the Xtender's output current given on the
type plate and the protection device selected for the input (see fig.
1a).
See chapter 4.2 - p. 10.
In a fixed installation where the neutral is connected to the earth at a
single installation point upstream of the Xtender, it is permissible to
carry out a connection of the neutrals in order to preserve an
unchanged earthing system downstream, independent of the
operating mode of the Xtender. This choice shows the advantage of
keeping the differential protection devices downstream of the
Xtender.
This connection (C) is not permitted if a socket is installed upstream
of the Xtender.
A protection device must be installed downstream of he source (G or
U) according to the local requirements and in compliance with the
applicable regulations and standards.
The neutral is earthed at a single point of the installation, downstream
of the source and upstream of the protection device(s) at the default
current (DDR). When several sources are available, each source must
have an earthed neutral. If the source has to be retained with an
isolated earthing system (IT) the applicable local provisions and
regulations must be applied.
A protection device dimensioned in dependence of the cable section
used may be installed downstream of the Xtender (main circuit
breaker before distribution). The cable section is to be dimensioned
according to the calculation table of maximum output current (fig. 1).
The Xtender has an internal current limitation the value of which is
stated on the type plate Fig. 1b (35).
The generator is dimensioned according to the requirements of the
user. Its rated current will determine the configuration adjustment
{1107} "maximum current of the AC source".
The protection device at the input of the Xtender must be
dimensioned according to the power output of the source at the
cable section used. It will not exceed a calibre equivalent to the input
current "I AC in" given on the type plate of the unit Fig. 1b (35).
If the Xtender is connected to an AC source by means of a plug, the
connection cable must not exceed a length of 2 m, and the socket
must remain permanently accessible. The socket will be protected by
a protection device of appropriate calibre. The connection of the
neutrals (C) is prohibited in this case.
Distribution to the users supplied by the grid or the generator when
this is present or by the Xtender within the limit of its power output
from energy stored in the battery. This distribution is carried out in
conformity with the local standards and regulations.