Pos. Denomination Description
10
L1/L2/L3
11
+BAT
12
-BAT
13
AC Input
14
AC Output

15 Control and display parts for the Xtender (fig. 4b)

See chapter 7.2 - p. 24.
Pos. Denomin
Description
ation
ON/OFF ON/OFF button
41
42
OFF
Light
for stoppage of
the unit
43
ON
Light
showing that the
equipment is in
operation
44
Charge
Light
showing that the
battery is being
charged
45
AC in
Light
showing
presence
correct
synchronised
input voltage
46
AC out
Light
showing
presence of a
voltage
output

16 Type plate elements (fig. 1b)

Pos. Denomination
31
Model
32
Pnom/P30
Installation and operating Instructions
Phase selection jumpers.
Positive pole battery connection
terminals
Negative
pole
connection terminals
Connection terminals for the
alternative
power
(generator or public network)
Connection terminals for the
device output.
Comments
The ON/OFF button allows the start up or complete stoppage
of the system such as it has been programmed. When there
are several units in the same system, each unit must be
started up or stopped individually using this button.
indicator
When the light indicator flashes it indicates the cause of the
stoppage of the unit, its imminent stoppage or the limitation of
its rated power output according to chapter 7.2 - p.24.
indicator
This indicator is glowing continuously when the device is
working. It flashes when the equipment is at a temporary
stop. Note: The equipment will restart automatically when the
conditions that led to the temporary stoppage have gone
away.
indicator
This indicator is glowing continuously when the charger is in
operation and has not yet reached the absorption phase.
It flashes twice during the absorption phase and once during
the maintenance phase.
If smart boost mode has been activated it is possible that this
indicator will go out temporarily when source backup is
required by users. (See chapter 6.2.6 - p. 19)
indicator
This indicator is glowing continuously when an alternative
the
voltage with correct values is present at the AC IN input (13)
of
of the device and the current limit {1107) set by the user has
and
not been reached. It flashes when this limit is reached (see
chapter 6.2.5 – p. 19).
indicator
This indicator is glowing continuously when an alternative
the
voltage of 230V is present at the device output. It flashes
when the device is in "load search" mode due to the absence
at
the
of users. (See chapter 6.2.3 – p. 16)
Description
Model
Rated power output / power for 30 minutes
Comment
See chapter 6.3.1. – p.22.
Jumper default at position L1
Carefully read chapter 4.5 – p.12
Take care with the polarity of the battery
and when tightening the clamp.
battery
See chapter 4.5.7 - p. 14.
supply
Note: It is imperative that the PE terminal
be connected.
See chapter 4.5.6 - p. 14.
Note: Increased voltages may appear on
the terminals, even in the absence of
voltage at the input of the inverter.
Xtender V1.3
Xtender
Comments
Page 32