Elements Of Connexion Cabinet (Fig 4A) - Studer Xtender XTH 5000-24 Installation And Operating Instructions Manual

Unit combining inverter, battery charger and transfer system
Hide thumbs Also See for Xtender XTH 5000-24:
Table of Contents

Advertisement

STUDER Innotec
Elem. Description
T
Non-secured grid
U
Public grid
V
Automatic
earth-
neutral connection
W
Galvanic isolator
X
Source reversing
switch
Y
Isolation
transformer

14 Elements of connexion cabinet (Fig 4a)

Pos. Denomination Description
1
ON/OFF
Main switch
2
Temp. Sens
3
Com. Bus
4
O / T
(Open
/
Terminated)
5
--
6
--
7
REMOTE
ON/OFF
8
AUXILIARY
CONTACT
9
--
Installation and operating Instructions
Comment
Distribution to users supplied exclusively via the present grid or the
generator.
This distribution is carried out in conformity with the local standards
and regulations.
The connection to the public grid imposes adherence to the local
standards and regulations at the responsibility of the installer. The
installation should, in principle, be checked and approved by an
official body.
This connection is deactivated by default. In may be used in certain
specific cases for automatically re-establishing the neutral system
type TT (TNC, TNS, TNC-S) when the Xtender is in inverter mode.
The activation is carried out via RCC-02/03 remote control
configuration {1485}. This operation may only be carried out by
qualified personnel, under the responsibility of these personnel, and in
conformity with the local standards and regulations. See 4.2.3– p.11
This device (optional) is generally used to reduce the risk of
electrolytic corrosion due to the direct current when a boat is
connected at the dock.
When the installation has more than one supply source, it is
necessary to install a switching device between the sources,
simultaneously switching the neutral and the phase(s) of these
sources. In all cases this device (manual or automatic) must
guarantee interruption of the connected source before its connection
to another source.
This device (optional) prevents the risk of galvanic corrosion due to
direct currents when a boat is connected at the dock.
Main on/off switch
Connector
for
the
temperature sensor
Double
connector
connecting peripherals such as
the
RCC002/03
or
Xtender units
Switch
for
terminating
communication bus.
3.3 V (CR-2032) lithium ion type
battery socket
Jumper for programming the
off/on switch by dry contact
Connection terminals for dry
on/off remote connection.
Auxiliary contact
Activation indicators for auxiliary
contacts 1 and 2
Comment
See chapter 7.1 - p 24.
battery
See chapter 6.4.2 – p. 24.
Only connect the original Studer BTS-01
sensor
for
See chapter 4.5.9 – p. 14.
The two termination switches (4) for the
other
communication
position T (terminated) except when both
connectors are in use.
the
Used as a permanent supply for the
internal clock. See chapter 6.2.11 - p 21.
See chapter 6.2.12 – p. 21 and fig. 8b
point (6) and (7). They are positioned at A-
1/2 and B-2/3 by default
See chapter 6.2.12– p. 21).
When the control via dry contact is not
being used, a bridge must be present
between the two terminals.
(See chapter 6.2.10– p. 21)
Take care not to exceed the admissible
loads
See chapter 6.2.10– p. 21
Xtender V1.3
Xtender
bus
both
remain
Page 31