Raypak XTherm Series Installation & Operating Instructions Manual page 42

Table of Contents

Advertisement

Boiler Menu
The Boiler View displays various items regarding ignition, temperature monitoring, and modulation rates. As well
as software and hardware information
Item
BOILER 1
BOILER 2
BOILER 3
BOILER 4
IGNITION
VENT WALL
LIMIT TEMP
EMS Vdc
FIRE RATE
SPEEDX 1000
OUTLET MAX
OPERATOR
DIFF
Pump Post
FLAME CUR
MASS
IDENTITY
ID CARD
ERROR CODE
Application
Description
ALL
Enables Boiler for operation
CASCADE
Enables Boiler for cascade operation
CASCADE
Enables Boiler for cascade operation
CASCADE
Enables Boiler for cascade operation
IDLE=no CFH; PREP=pre-purge or inter-purge between trials for ignition; IGN=trial for
ignition; BURN=burner operating; POST=post purge; HARD=a hard lockout fault has
occurred requiring manual reset (Ignition Lockout or manual high limit); and SOFT=a
soft lockout fault has occurred which interrupts the heating cycle (any safety other than
ALL
ignition or manual high limit).
The CFH will resume after the soft lockout fault has been corrected and a 15 min.
waiting period has expired.
Not available
Not Available
ALL
Current Outlet-Limit temperature
ALL
Current EMS signal in Volts DC
ALL
PIM firing rate
ALL
Blower speed in revolutions per minute (rpm) x 1000
Defines Max Outlet temperature offset above Target Setpoint (Press and hold up and
H Mode 1, 2, 3
down arrows for 3 seconds to enable adjustment). see VERSA IC manual, catalog
5000.72.
ALL
Operator Potentiometer setting on PIM
ALL
Current auto differential – Fixed by PIM
ALL
Sets the length of the boiler pump purge
ALL
Flame current in micro-amps (µA)
ALL
Thermal mass recovery see VERSA IC manual, catalog 5000.72.
ALL
Identifies the unit as boiler, water heater or pool heater
ALL
Identifies Raypak Identity Card
ALL
Current Error Code
Table T: Boiler Menu
42

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Xtherm 2505Xtherm 3005Xtherm 3505Xtherm 4005

Table of Contents