the Indirect Supply sensor (S6) and the Target Max
setting when using the Indirect DHW sensor (S5). The
Boiler/Injection Pump (P1) runs during all heat calls
regardless of priority. The Indirect DHW Pump (P3)
runs during an indirect call for heat with no "off" delay.
The Boiler/Injection Pump (P1) is delayed "off" as user
defined in the BOILER menu and the System Pump
(P2) is delayed "off" in the ADJUST menu. The system
pump (P2) runs whenever the system is enabled for
heating and the outdoor air temperature is lower than
the WWSD temperature setting (if utilized) unless an
indirect call for heat is present.
NOTE: A Tank Aquastat can be used in lieu of the
Indirect DHW Sensor (S5). See the VERSA IC man-
ual for additional details.

Domestic Hot Water

When designing the water piping system for domes-
tic hot water applications, water hardness should be
con-sidered. Table H indicates the suggested flow
rates for soft, medium and hard water. Water hardness
is ex-pressed in grains per gallon.
Soft (2-4)
Med (5-15)
Sys Ret
Supply
Sys
Supply
Temp
Temp
Flow
Temp
(F)
(F)
GPM
(F)
80
144
74
139
100
144
108
139
120
149
164
149
140
169
164
169
Soft (2-4)
Med (5-15)
Sys Ret
Supply
Sys
Supply
Temp
Temp
Flow
Temp
(F)
(F)
GPM
(F)
80
148
98
143
100
148
139
143
120
150
222
150
140
170
222
170
HIGH FIRE CONDITIONS
Flow rates determined based on max temperature rise of 30ºF. Pipe size selected based on 7.5 ft per sec maximum velocity.
*Must utilize optional cupro-nickel tubes. If over 25 grains per gallon, a water softener/treatment system must be utilized.
**Caution: For scale-free operation with "Hard Water" (16-25 grains per gallon of total hardness), the operating control must NOT be set
higher than 130ºF. For higher than 130ºF operation, a water softener/treatment system must be utilized.
***Care should be given to prevent over-softening of the water as over-softened water can become aggressive. Cupro-nickel tubes are
recommended for water softened below 5 grains per gallon.
Model 2505
Hard (16-25)
Pipe max eq ft
(164gpm@6.8ft.hd.)
Sys
Supply
Sys
Flow
Temp
Flow
3"
GPM
(F)
GPM
81
137
83
100
122
137
128
100
164
149
164
100
164
169
164
100
Model 3505
Hard (16-25)
Pipe max eq ft
(222gpm@2.7ft.hd.)
Sys
Supply
Sys
Flow
Temp
Flow
3"
GPM
(F)
GPM
106
143
106
155
143
155
222
150
222
222
170
222
Table H: Domestic Water Heater Flow Rate Requirements
Fig. 21: WH Units - Single Water Heater with Tank
H Units - Single Boiler with Process Tank
WH – Direct DHW Configuration
When the unit is ordered as a "WH" configuration, the
only application available to it is direct DHW with sin-
gle or multiple heaters (Maximum 4 heaters). The tank
temperature is controlled by the System sensor (S3).
The Boiler/Injection Pump (P1) runs during any call for
heat. The System Pump (P2) output is active whenev-
er the system is enabled. The Boiler Pump is delayed
"off" as user-defined in the BOILER menu.
Soft (2-4)
Med (5-15)
Supply
Sys
Supply
Temp
Flow
Temp
4"
(F)
GPM
(F)
350
148
84
139
350
148
119
139
350
150
190
150
350
170
190
170
Soft (2-4)
Med (5-15)
Supply
Sys
Supply
Temp
Flow
Temp
4"
(F)
GPM
(F)
100
148
112
146
100
148
158
146
100
150
253
150
100
170
253
170
19
Model 3005
Hard (16-25)
Pipe max eq ft
(190gpm@2.1ft.hd.)
Sys
Supply
Sys
Flow
Temp
Flow
3"
GPM
(F)
GPM
97
139
97
146
139
146
190
150
190
190
170
190
Model 4005
Hard (16-25)
Pipe max eq ft
(253gpm@3.5ft.hd.)
Sys
Supply
Sys
Flow
Temp
Flow
3"
GPM
(F)
GPM
115
146
115
165
146
165
253
150
253
253
170
253
4"
110
110
110
110
4"
100
100
100
100

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Xtherm 2505Xtherm 3005Xtherm 3505Xtherm 4005

Table of Contents