end of the actuator motor. This will allow the motor
to rotate into alignment with the bracket.
5.
Align the motor with the valve mounting bracket.
6.
With the motor and bracket aligned, slide the lock
bracket forward to secure the motor to the anti-ro-
tation bracket and tighten the 7/16" hardware.
Condensate Switch
The condensate switch is located in the flue collector
of the condensing exchanger. The switch will shut the
unit down in the event of a blockage in the condensate
management system.

User Interface

Fig. 51: Condensate Switch
The Touch Screen (TS) user interface uses a high
definition 7" capacitive screen. It includes an exten-
sive graphical library used to represent different pipe
configurations, error location, and operation of the unit.
The TS has the same basic menu distribution as the
original LCD Display, when pressing the MENU button
the menu bar becomes visible at the bottom of the
screen allowing navigation through four addition sub
menus (VIEW, ADJUST, BOILER, and TOOLS).
For detailed descriptions of the various screens, page
flows and basic instructions, consult the Touch Screen
Quick Start User Guide (Catalog #5000.74) and
VERSA IC Control I&O Manual (Catalog #5000.72).
Adjusting the XTherm Setpoint
Item
OUTDOOR
Target
SUPPLY
IND Supply
Boil OUTLET
Boil INLET
Boil ΔT
DHW SUPPLY
TANK
BOILER STATUS
Application
Description
Outdoor air temperature, available when TARGET = RSET in ADJUST menu
H MODE 1, 2, 3
Current target temperature, available when Target = SETP in the ADJUST menu (default), and
H MODE 1, 2, 3
(EMS / MODB)
Current system supply temperature
H MODE 1, 2, 3
Current temperature being supplied to the indirect system
H MODE 3
All
Current boiler outlet temperature
All
Current boiler inlet temperature
All
Current temperature difference between boiler outlet and boiler inlet
Current indirect DHW supply temperature, requires IND Sensor = ON in ADJUST menu
H MODE 2, 3
WH
Current tank temperature
All
IDLE, PREP, IGN, MOD RATE %, POST, SOFT, HARD
Use the MENU button to open the menu options, select
the ADJUST menu, go to System Settings page. Once
in the system settings screen use the Setpoint item.
Adjust the setpoint using the UP and DOWN arrow.
After making the setpoint selection press SET button
to apply the changes (a confirmation bar will turn
green showing that value has been applied). Minimum
setpoint is 50ºF; maximum is 220ºF for H models,
150ºF for WH models and 104ºF for P models. The
default setpoint is 180ºF for H models, 125ºF for WH
models and 80ºF for P models.
View Menu
The VIEW menu (See Table P) is the default menu.
It displays sensor temperatures, the modulation rate
of the blower, heater cascade status, pump operation
and CFH information. Some of the items displayed
are mode specific and are only observable when its
corresponding mode is active.
Menu - Initial Adjustment
To change settings use the MENU key to scroll to the
SETUP/ADJUST menu. The ADJUST menu allows
the installer to make adjustments to items shown in
Table R.
Refer to the VERSA IC Control I&O Manual (Catalog
#5000.72) for detailed setup instructions.
Table R: View Menu
40
Fig. 52: User Interface