an additional room(s) of sufficient volume so that the
com-bined volume of all spaces meets the criteria for
a room large in comparison (NFGC). The total input of
all gas utilization equipment installed in the combined
space shall be considered in making this determina-
tion. Each opening shall have a minimum free area
of 1 in.
per 1,000 BTUH (2,225 mm
2
total input rating of all gas utilization equipment in the
confined space, but not less than 100 in.
One opening shall commence within 12 in. (305 mm)
of the top, and one opening shall commence within
12 in. (305 mm) of the bottom of the enclosure. The
minimum dimension of air openings shall be not less
than 3 in. (76 mm) in any direction.
All Air from Outdoors
The confined space shall communicate with the out-
doors in accordance with one of the methods below.
The minimum dimension of air openings shall not be
less than 3 in. (76 mm) in any direction. Where ducts
are used, they shall be of the same cross-sectional
area as the net free area of the openings to which they
connect.
1. Two permanent openings, one commencing
within 12 in. (305 mm) of the top, and one com-
mencing within 12 in. (305 mm) of the bottom of
the enclosure, shall be provided. The openings
shall communicate directly, or by ducts, with the
outdoors or spaces (crawl or attic) that freely com-
municate with the outdoors.
a. Where directly communicating with the out-
doors or where communicating to the outdoors
through vertical ducts, each opening shall
have a minimum free area of 1 in.
BTUH (550 mm
of all equipment in the enclosure.
b. Where communicating with the outdoors
through horizontal ducts, each opening shall
have a minimum free area of 1 in.
BTUH (1,100 mm
ing of all equipment in the enclosure.
2. One permanent opening, commencing within 12
in. (305 mm) of the top of the enclosure, shall be
permitted where the equipment has clearances
of at least 1 in. (25 mm) from the sides and back
and 6 in. (152 mm) from the front of the appliance.
The opening shall directly communicate with the
out-doors or shall communicate through a vertical
or horizontal duct to the outdoors or spaces that
freely communicate with the outdoors, and shall
have a minimum free area of:
per kW) of the
2
(645 cm
2
per 4,000
2
per kW) of total input rating
2
per 2,000
2
per kW) of total input rat-
2
a. 1 in.
per 3,000 BTUH (740 mm
2
the total input rating of all equipment located
in the enclosure, and
b. Not less than the sum of the areas of all vent
connectors in the confined space.
WARNING: Do not use the "one permanent opening"
method if the equipment room is under negative-
).
2
pressure conditions.
Canadian Installations
CAUTION: All combustion air must be drawn from
the air outside of the building; the mechanical equip-
ment room must communicate directly with the
outdoors.
1. Ventilation of the space occupied by the heater
shall be provided by an opening(s) for ventilation
air at the highest practical point communicating
with the outdoors. The total cross-sectional area
of such an opening(s) shall be at least 10% of the
area required in 2. and 3. (below), but in no case
shall the cross-sectional area be less than 10 in.
(65 cm
).
2
2. For heaters using a barometric damper in the
vent system there shall be a permanent air supply
opening(s) having a cross section area of not less
than 1 in.
per 7,000 BTUH (320 mm
2
up to and including 1 million BTUH, plus 1 in.
per 14,000 BTUH (160 mm
of 1 million BTUH. This opening(s) shall be either
located at or ducted to a point not more than 18 in.
(450 mm) nor less than 6 in. (152 mm) above the
floor level. The duct can also "goose neck" through
the roof. The duct is preferred to be straight down
and terminated 18 in. (450 mm) from the floor, but
not near piping. This air supply opening require-
ment shall be in addition to the air opening for
ventilation air required in 1. (above).
WARNING: Care must be taken to ensure that the
equipment room is not under negative-pressure
conditions.
3. For heaters not using a barometric damper in the
vent system, and when air supply is provided by
natural air flow from outdoors for a power burner
and there is no draft regulator, drafthood or sim-
ilar flue gas dilution device installed in the same
space, in addition to the opening for ventilation air
required in 1., there shall be a permanent air sup-
ply opening(s) having a total cross-sectional area
of not less than 1 in.
13
per kW) of
2
per kW)
2
per kW) in excess
2
for each 30,000 BTUH (74
2
2
2