Raypak XTherm Series Installation & Operating Instructions Manual page 41

Table of Contents

Advertisement

Item
Application
TARGET
H MODE 1, 2, 3
TANK SETP
WH
TANK DIFF
WH
POOL SETP
P
POOL DIFF
P
POOL MAX
P
MODE
H MODE 1, 2, 3
SETPOINT
H MODE 1, 2, 3
OUT START
H MODE 1, 2, 3
OUT DESIGN
H MODE 1, 2, 3
Boil START
H MODE 1, 2, 3
Boil DESIGN
H MODE 1, 2, 3
TARGET MAX
H MODE 1, 2, 3
TARGET MIN
H MODE 1, 2, 3
TARGET DIFF
H MODE 1, 2, 3
IND SENSOR
H MODE 1, 2, 3
IND SETP
H MODE 2, 3
DHW DIFF
H MODE 2, 3
IND SUPPLY
H MODE 2, 3
DHW PRIORITY
H MODE 2
PRI OVR
H MODE 2, 3
SYS PURGE
All
MIX TYPE
H / WH / P MIX
MIX TARGET
H / WH / P MIX
MIX LOCK
H / WH / P MIX
MIX TRIM
H / WH / P MIX
MIX SPEED
H / WH / P MIX
MIX INV
H / WH / P MIX
WWSD
H MODE 1, 2, 3
UNITS
All
MODBUS
All
ADDRESS
All
DATA TYPE
All
BAUD RATE
All
PARITY
All
* Maximum operator dial setting.
Range
Description
RSET <> SETP
RSET = Outdoor Reset, SETP =Setpoint
OFF, 50°F to 150°F
Tank set point temperature
2°F to 10°F
Tank Differential temperature
50ºF to 104ºF, 106ºF
Pool set point temperature
1ºF to 5ºF
Pool Differential temperature
110ºF to 120ºF
Pool Maximum temperature
1,2,3
Piping and application configuration.
Boiler target temperature while a heat demand is present for set-
50°F to 220°F
point operation
35°F to 85°F
Outdoor starting temperature - outdoor reset
-60°F to 45°F
Outdoor design temperature - outdoor reset
Starting boiler target temperature when the outdoor temperature
35°F to 150°F
is at outdoor start outdoor reset
Design boiler target temperature when the outdoor temperature is
70°F to 200°F
at outdoor design outdoor reset
100°F to PIM value*
Maximum target system temperature
Minimum target system temperature
OFF, 50°F to 190°F
2°F to 42°F
Differential for target system temperature
OFF <> ON
Selects whether a DHW sensor is used for indirect DHW tank
OFF, 50°F to 180°F
Target Indirect DHW Temperature, requires IND SENSOR = ON
Differential for the target indirect DHW tank temperature, requires
2°F to 10°F
IND SENSOR = ON
Target boiler temperature for the DHW heat exchanger during
OFF, 50°F to PIM value*
indirect DHW operation, requires IND SENSOR = OFF
Selects whether or not Indirect DHW priority is active during indi-
OFF <> ON
rect DHW operation
Au, 0:10hr to 2:00hr
Sets the length of the indirect DHW priority override time
OFF, 0:20min to 20:00min
Sets the length of the system pump post purge
H (VALVE, PUMP, PLNT)
Selects the type of control depending on pipe configuration for
WH (1 <> 2)
CWP
Inlet Target Temperature
50°F to 140°F
The equipment will trigger a warning when "MIX Target" is not
OFF <> ON
reached within 7 minutes. MIX LOCK = ON; Alarm and lockout,
MIX LOCK = OFF; Alarm only
This adjustment is for various types and sizes of units as well as
-5 to 5
various actuator motor speeds and types supplied by Raypak
SLOW <> MED <> FAST
This setting defines speed of response.
This option is related to the use of spring return actuators with a
OFF <> ON
proportional valve
The system warm weather shutdown temperature outdoor reset,
40°F to 100°F
requires TARGET = RSET
deg F <> deg C
Show units using icons in display
OFF <> MNTR <>
ModBus Operating Mode: Off, Monitor, Temp Control, Rate
TEMP <> RATE
Control
1 to 247
ModBus slave address
RTU <> ASCI
Modbus data type
2400 <> 9600 <> 19K2 <>
57K6 <> 115K
NONE <> EVEN <> ODD
Table S: Setup/Adjust Menu
41
Default
SETP
125°F
5
80ºF
2ºF
110ºF
1
180°F
70°F
10°F
70°F
180°F
220°F
50°F
10°F
OFF
140°F
6°F
180°F
OFF
1:00hr
20 seconds
H VALVE
WH 2
120°F
OFF
0
MED
OFF
70°F
deg F
MNTR
1
RTU
19K2
EVEN