Honeywell IntelliPath Series Installation And Setup Manual page 34

Internet and cellular communicator
Hide thumbs Also See for IntelliPath Series:
Table of Contents

Advertisement

LTE-I Installation and Setup Guide
PROMPTS
Lynx Panic Y/N
30
(N)_
Zone Trigger Mode provides six hardwire zone input triggers by making connections to the communicator's zone
terminals and programming the appropriate zone trigger options below. Zones are numbered 1-7, with zone 2 serving as a
reporting zone only (see Bell Output Zone below).
Bell Output Zone 1 (and 2): The zone 1 terminal can detect both pulsed and steady signals. If connecting the bell output
to the communicator zone causes a bell fault on the control panel, enable the "Trip Inputs 1 or 2" option. The
communicator reports an alarm on zone 1 (fire) when it detects a pulsed signal and an alarm on zone 2 (burglary) when it
detects a steady signal.
UL/UL: Use of the Bell output is not supported.
Telco Zone and Open/Close Zone: Dedicated zones can be assigned as the Telco fault zone and/or an open/close
(arm/disarm) reporting zone. When triggered, these zones report a Telco line fault or open/close report respectively, in
ADEMCO High-Speed format. Connect the appropriate trigger from the control panel to the selected zone input for each of
these options.
Input Trigger Types: Triggering of each zone input can be programmed to cause an alarm under one of the following
conditions:
 (V+), where a positive voltage causes an alarm for normally low connections (voltage trigger, NO, NC)
 (V–), where a ground trigger causes an alarm for normally high connections (open collector, NO, NC)
 (EOLR) End of Line Resistor, where the input is supervised by a 2K EOL resistor. The zone can be triggered by
open collector, voltage trigger, NO, NC.
UL/UL: Set V+ to inverted, and V– as non-inverted.
Inverted Trigger: Zones can be programmed for inverted trigger, where the alarm and normal states of the zones are
inverted; this can serve a fail-safe supervisory purpose for certain installations.
Restore and Delayed Reports: Zone inputs can be programmed for restore reporting, and for delayed reporting (NOT for
UL installations) allowing time for the user to abort false alarms.
UL/ULC: Zone restoral must be enabled.
Report Only if Armed option: To help eliminate redundant reports, zone alarms can be restricted to report only if a
conditional zone is triggered (armed). If this feature is desired, the conditional zone is automatically used as the "arming"
zone. Connect the appropriate control panel trigger to the conditional (arming) zone. The trigger must be programmed as
necessary in the control panel.
The conditional (arming) zone on the communicator is a different dedicated zone for each programming mode, as follows:
IMPORTANT: If any zone (zones 1-6 in zone trigger mode) is set for Report Only if Armed, the conditional (arming) zone
becomes unavailable for reporting (as it is reserved for the "arming" trigger connection).
PROMPTS
Trip Inputs 1or2
31
w/Bell Out (N)_
OPTIONS
[Y], [N]
Important Information Regarding Zone Input Options
Mode
Zone Trigger
OPTIONS
[Y], [N]
Applies only if used with a Lynx, LynxR or
LynxR-EN controls where the communicator (or LRR) trigger is
connected to the communicator's zone terminal.
Reports a Panic alarm on zone 3 when the communicator detects
a single pulse on zone 1.
No restores are generated for a Panic alarm.
UL/ULC: The LYNX controls have not been evaluated with this
communicator.
Conditional (Arming) Zone
7
Use if the zone 1 connection to the control panel's bell
output causes a bell fault at the control panel.
NOTES:
1. If used, EOLR trigger type is not available for zones 1
and 3.
2. Do not use with Lynx controls.
30
DESCRIPTION
DESCRIPTION

Hide quick links:

Advertisement

Table of Contents
loading

This manual is also suitable for:

Intellipath lte-ivIntellipath lte-iaIntellipath lte-ic

Table of Contents