Honeywell IntelliPath Series Installation And Setup Manual page 33

Internet and cellular communicator
Hide thumbs Also See for IntelliPath Series:
Table of Contents

Advertisement

PROMPTS
IP Flt Time
23
(60 mins)_
Cell Flt Time
24
(60 mins)_
Notify Panel Of_
25
(Neither Fault)_
Flt Rel ON Y/N
26
(N)_
Pwr Loss Rpt
27
Y/N (Y)_
Low Bat Rpt Y/N
28
(Y)_
Tamper Rpt Y/N
29
(Y)_
OPTIONS
[00-99]
[00-99]
[Neither fault]
[Both IP and Cell Faults]
[Y], [N]
[Y], [N]
[Y], [N]
[Y], [N]
Section 3: Programming the Communicator
This prompt appears only if comm. path includes IP.
In the event there is a loss of contact with the network over the
Ethernet connection, enter the time delay (in minutes) before the
communicator notifies the central station. IP failure will always be
sent to the central station as Primary Communication Path Failure.
UL/ULC: Must be one (01) minute.
This prompt appears only if comm. path includes Cell.
In the event the communicator detects a communication path
failure, enter the time delay (in minutes) before the communicator
notifies the central station. A cell failure will always be sent to the
central station as Secondary Communication Path Failure.
UL/ULC: Must be one (01) minute.
This prompt appears only if comm. path is set to IP & Cell.
If "Both IP and Cell Fault" is selected, the device will only notify the
control panel if both communication paths fail, but will always send
notification of either failure to the central station.
NOTE: The fault relay output (if programmed) will be triggered only
if "Both IP and Cell Faults" is selected. (If the "Cell Fault Time" and
"IP Fault Time" options are set to zero, faults will not be reported.)
Press the [space] key to scroll through choices.
UL/ULC: Must be set to "Both IP and Cell Faults".
If enabled, the fault open collector output is normally energized to
ground, and de-energizes (open circuit) in the event of a
communicator fault. For conditions that trip the fault relay refer to
Supervision Features in Section 1.
Set to [Y] if fail-safe mode is desired.
See Wiring the Fault Relay in Section 2.
UL/ULC: Must be set to "Y".
Sends a primary power loss report to the central station within 1-3
hours after its detection. A restore report is sent within 1-3 hours
after power is restored.
UL Standard Installations (using transformer and battery): Must
be set to "Y".
ULC Commercial Fire & Burglary Installations (powered from
the control panel): Must be set to "N."
Sends a low-battery report when a low battery condition exists. A
low-battery restore is automatically sent when the low battery
condition clears.
UL Standard Installations (using transformer and battery): Must
be set to "Y".
ULC Commercial Fire & Burglary Installations (powered from
the control panel): Must be set to "N."
Sends a tamper report when the communicator detects a tamper
condition. A tamper restore is automatically sent when the tamper
condition clears.
UL/ULC: Must be set to "Y".
29