Power, software, and circuit pack installation
...................................................................................................................................................................................................................................
Procedure 5-2: Fan unit test
Overview
This test verifies the correct working of the fan unit in the 1675 LambdaUnite MSS
subrack. The test should be carried out for each installed E.
Procedure
Proceed as follows to test the correct functionality of the fan unit:
...................................................................................................................................................................................................
1
Check the LED status indication on the back of the fan unit.
Result:
LED should be off.
Figure 5-3 Fan unit LEDs
...................................................................................................................................................................................................................................
5-8
The "PWR O " LED on the fan unit should be illuminated, the "FAULT"