Specifications; Temperature Controller Ratings; Control Output Unit Ratings; Current Transformer Ratings - Omron E5EX–H Manual

Table of Contents

Advertisement

E5EX–H

Specifications

Temperature Controller Ratings

Supply voltage
Operating voltage range
Power consumption
Input
Current Transformer input
Control output
Operating mode
Alarm output
Heater burnout alarm output
Setting method
Indication method
Other functions
Approved standards

Control Output Unit Ratings

Relay Output Unit
SSR Output Unit
Voltage Output Unit (for driving SSR)
Note: The control output is optically insulated from the internal circuits.

Current Transformer Ratings

Max. continuous heater current
Dielectric strength
Vibration
Weight
2
100 to 240 VAC, 50/60 Hz
85% to 110% of rated supply voltage
Approx. 10 VA (at 100 VAC) to 15 VA (at 240 VAC)
Thermocouple (K/J/T/E/R/S/L/U) or temperature resistance thermometer (Pt100/JPt100) selectable
See Current Transformer Ratings.
See Control Output Unit Ratings.
ON/OFF or PID with auto-tuning
Relay output: SPST–NO; 3 A, 250 VAC
Relay output: SPST–NO; 1 A, 250 VAC
Digital setting via up and down keys
Digital indication (character heights: 11 mm and 8 mm)
Upper and lower limits for set value
Key protection
Input shift
Display unit selection (°C/°F)
Normal and reverse output selection
Watchdog timer function (Detects failures in the CPU and restores the CPU.)
UL (File No. E68481)
CSA (File No. LR59623)
SEV
E53–R
SPDT; 5 A, 250 VAC (resistive load)
E53–S
SPST–NO; 1 A, 75 to 250 VAC
E53–Q
40 mA, 12 VDC; NPN (with short-circuit protection)
E53–Q3
20 mA, 24 VDC; NPN (with short-circuit protection)
E53–Q4
20 mA, 24 VDC; PNP (with short-circuit protection)
50 A
1,000 VAC
50 Hz (approx. 10G)
E54–CT1: Approx. 11.5 g; E54–CT3: Approx 50 g