Specifications
■ Characteristics
Indication accuracy
Influence of temperature
(See note 2.)
Influence of voltage
(See note 2.)
Proportional band ( P )
Integral time (I)
Derivative time (D)
Control period
Manual reset value
Alarm settings range
Sampling period
Insulation resistance
Dielectric strength
Vibration resistance (Error)
Shock resistance (Error)
Weight
Memory protection
EMC
Pending standards
Note 1: The indication accuracy of K thermocouples in the -200 to 1300°C range, T and N thermocouples at a temperature of -100°C max., and
U and L thermocouples at any temperature is ± 2°C ± 1 digit maximum. The indication accuracy of the B thermocouple at a temperature of
400°C max. is not specified. The indication accuracy of the R and S thermocouples at a temperature of 200°C max. is ± 3°C ± 1 digit max.
2: For E5EZ-PRR@03-model products, in order to satisfy the conduction and emission specifications of EN61326CLASSA, a magnetic ring
(TDK:ZAT1730-0730) should be added to the communications line between the K3SC unit and the controller.
32
Digital Position-Proportional Controllers
Thermocouple:
(displayed value ± 0.5 % or ± 1°C, whichever is largest) ± 1 digit max. (see note 1)
Platinum Resistance Thermometer:
(displayed value ± 0.5 % or ± 1°C, whichever is largest) ± 1 digit max.
Analog Input: ± 0.5% FS ± 1 digit max.
Potentiometer Input: ± 5% FS ± 1 digit max.
R, S, and B thermocouple inputs:
( ± 1% of PV or ± 10°C, whichever is greater) ± 1 digit max.
Other thermocouple inputs:
( ± 1% of PV or ± 4°C, whichever is greater) ± 1 digit max.
* ± 10°C for -100°C or less for K sensors
Platinum resistance thermometer inputs:
( ± 1% of PV or ± 2°C, whichever is greater) ± 1 digit max.
Analog inputs:
( ± 1% of FS) ± 1 digit max.
0.1 to 999.9°C (unit: 0.1 EU)
0 to 3999 s (in units of 1s)
0 to 3999 s (in units of 1s)
1 to 99 s (in units of 1s)
-10.0% to 110.0% (in units of 0.1%)
-1999 to 9999 (decimal point position depends on input type)
500 ms
20M Ω min, 2 seconds (500 VDC)
2000VAC,50 or 60Hz for 1min (at different stages of charging)
10 to 55Hz, 20m/s
for 10min each in X,Y, and Z directions
2
100m/s
,3 times each in 3
2
Controller : Approx. 260g
EEPROM (non-volatile memory) (number of writes: 100,000 operations)
Emission enclosure:
Emission AC mains:
Immunity ESD:
Immunity RF interference:
Immunity-conducted disturbance:
Surges (shocks):
UL61010C-1,CSA C22.2 No.1010.1 meets the requirements of EN61326,EN61010-1(IEC61010-1)
E5EZ-PRR
With floating control, 1 to 3999 s
EN55011(GB/T 6113.1,2)
EN55011(GB/T 6113.1,2)
IEC61000-4-2(GB/T 17626.2)
IEC61000-4-3(GB/T 17626.3):
EC61000-4-6(GB/T 17626.6):
IEC61000-4-5(GB/T 17626.5):
1 group, type A
1 group, type A (see note 2)
4kV contact discharge (series 2)
6kV air discharge (series 3)
10V/m, 80MHz-1GHz (series)
3V(0.15-80MHz) (series 3)
2kV power supply line (series 3)
1kV I/O signal line (series 4)