6 Operation
6.6 Examples for Parameterization
6.6.3

Application as I/O Mirror via Ethernet Connection

Conceptual Formulation
Parameterize 2 SICAM I/O Units using the factory settings; one SICAM I/O Unit acts as I/O mirror server
and one SICAM I/O Unit as I/O mirror client.
Parameterize the threshold voltages of the 6 binary inputs.
Parameterize the indications and modes of the 6 binary outputs (relay outputs).
If the port numbers set by default in the SICAM I/O Units in the network are blocked, change them. The
port numbers of the SICAM I/O Unit – server and of the SICAM I/O Unit – client have to be identical.
Enter the server IP address in the I/O mirror client.
Use the hardware configuration according to Figure 5-1 with Ethernet connection.
Setting of the SICAM I/O Unit – Server with Ethernet Communication in I/O Mirror Server Mode
Figure 6-68
Setting of 6 Binary Inputs of the SICAM I/O Unit – Server
Parameterize the threshold value voltages of the binary inputs according to Figure 6-65.
Route the Indications from Remote to the 6 Binary Outputs of the SICAM I/O Unit – Server
Parameterize the indications and modes of the binary outputs according to Figure 6-66.
120
Setting of the Ethernet Communication for I/O Mirror Server
SICAM I/O Unit, 7XV5673, Device Manual
E50417-H1040-C484-A3, Edition 05.2012