13 Operating Parameters

13.1 Process Connections

13.1
Process Connections
13.1.1

Binary Inputs

Threshold value voltage
can be set for all binary inputs individually
Software filter time
can be set for each terminal block individually
Binary input indication
can be set for all binary inputs individually
13.1.2

Binary Outputs (Relay Outputs)

Indication
(can be set individually for all relay outputs)
Invert source
(can be set individually for all relay outputs)
Operating mode
(can be set individually for all relay outputs)
214
Parameter
Parameter
Default Setting
19 V
1 (*2) ms
For example for Terminals P8/9:
Binary input 1 - Terminal block P
Default Setting
-none-
no
Persistent
SICAM I/O Unit, 7XV5673, Device Manual
E50417-H1040-C484-A3, Edition 05.2012
Setting Range
19 V
88 V
176 V
2 ms to 120 000 ms
Arbitrary text; name of
the indication
Settings
-none-
Device OK
Battery Failure
Settings Load
Settings Check
Settings Activate
Modbus TCP OK
Ethernet Link Error
Modbus Serial OK
Time Synchronization Error
Primary NTP Server Error
Secondary NTP Server Error
Daylight Saving Time
Ethernet Link 2 Error
Default IP Address
Indication 1 from Remote
Indication 2 from Remote
Indication 3 from Remote
Indication 4 from Remote
Indication 5 from Remote
Indication 6 from Remote
Binary In 1 - Terminal block N
Binary In 2 - Terminal block N
Binary In 3 - Terminal block N
Binary In 1 - Terminal block P
Binary In 2 - Terminal block P
Binary In 3 - Terminal block P
I/O Ethernet OK
I/O Ethernet Fail > 0.05 %
I/O Serial OK
I/O Serial Fail > 0.05 %
I/O Mirror OK
no
yes
Persistent
Persistent with fail safe
Pulse
Pulse with retrigger