Section: BURNER CONTROLS
Burner Controls
SM burners shipped less Primary Control from RWB
shall require Model 7575P Primary Control be installed
with valve-on delay and motor-off delay to meet CSA
B140.0 per wiring in Figure 9B.
GeniSys 7505 & 7575
SM burners shall use the 7575P only.
Fire or Explosion Hazard
Can cause severe injury, death, or
property damage.
The control can malfunction if it gets wet, leading to
y
accumulation of oil or explosive oil vapors.
y
Never install where water can flood, drip or condense
on the control.
Never use a control that has been wet - replace it.
y
Features
○
Thermostat / Operating and Limit Control Compatible
○
Welded Relay Protection
○
Limited Recycle
○
Limited Reset
○
3 Status Lights
○
Valve-On Delay / Motor-Off Delay (Field programmable
with 52082 Contractor Tool)
○
15 Second Lockout Time
○
Interrupted or Intermittent Duty Ignition
○
Technician Pump Priming Mode
○
Disable Function
○
Communication Port(s)
Figure 8A – 7505 Control
Reset Button with Red Light
Yellow Light
Green Light
Thermostat Terminals
12
Wiring
All heating appliances must have HIGH
LIMIT protection to interrupt electrical
power and shutdown the burner if
operating or safety controls fail and
cause a runaway condition.
Follow the appliance manufacturer's wiring diagrams
y
and note all required safety controls.
Typical safety controls include high temperature or
y
pressure limits, low water cutoffs, pressure relief
valves and blocked flue sensing switches.
Verify all limit and safety controls are installed
y
and functioning correctly, as specified by the
manufacturer, applicable safety standards, codes and
all authorities having jurisdiction.
Ensure that the appliance is free of oil and oil vapor
y
before starting or resetting the burner.
GeniSys wiring label colors may not match the wire
y
colors of the burner or other manufacturers' controls.
The GeniSys Control should be wired according to
y
the appliance manufacturer's instructions.
Communication Port 2
Communication Port 1
Explosion, Fire, Scald,
and Burn Hazard
Incorrect Wiring Will
Result in Improper
Control Operation
Wiring
Connections
Cad Cell
Connections