Potential for Fire, Smoke and Asphyxiation Hazards
Incorrect installation, adjustment, or misuse of this burner could result in death, severe
personal injury, or substantial property damage.
To the Homeowner or Equipment Owner:
Please read and carefully follow all instructions
provided in this manual regarding your responsibilities
in caring for your heating equipment.
Contact a professional, qualifi ed service agency for
installation, start-up or service work.
READ THESE INSTRUCTIONS AND SAVE FOR
REFERENCE.
CORPORATION
To the Professional, Qualifi ed Installer or Service
Agency:
Please read and carefully follow all manual instructions
and any supplements provided, before installing,
starting, or servicing this burner or heating system.
The Installation must be made in accordance with all
state and local codes having jurisdiction.

Advertisement

Table of Contents
loading

Summary of Contents for Beckett SDC 24 VDC

  • Page 1 CORPORATION 24 Vdc Oil Burner Manual Potential for Fire, Smoke and Asphyxiation Hazards Incorrect installation, adjustment, or misuse of this burner could result in death, severe personal injury, or substantial property damage. To the Homeowner or Equipment Owner: To the Professional, Qualifi ed Installer or Service Agency: Please read and carefully follow all instructions provided in this manual regarding your responsibilities...
  • Page 2: Table Of Contents

    D. Regular Service/Maintenance ........11 have DC voltage charging systems capable of Troubleshooting ............12 sustaining the specifi ed voltage requirements. For other equipment applications, please contact Replacement Parts ............ 14 Beckett Technical Services at 1-800-645-2876. Limited Warranty Information ........16...
  • Page 3: Prepare Before Installing

    Outlet pressure: Note 1 outlined in the table to the right. Dimensions Height (maximum): 11 ½ inches For applications beyond these limits, consult Beckett Width (maximum): 14 3/8 inches Technical Service at 1-800-645-2876. Depth (chassis only): 6 9/16 inches Air tube diameter: 4 inches...
  • Page 4: General Information

    Finish tightening with a 5/8” open-end wrench. Figure 1. Typical Burner Nameplate General Model Information R.W. Beckett Serial Number Manufacturer’s Settings Including Date Code R.W. Beckett Specification Number and Revision ELYRIA OHIO U.S.A. Rating Information Model " AFG " MFR'S SETTINGS...
  • Page 5: Check/Adjust Electrodes

    Section: Nozzle Assembly Maintenance Correct Nozzle and Flow Use care when removing or Rate Required installing an oil nozzle Incorrect nozzles and fl ow rates could A damaged nozzle could cause impaired combustion, result in impaired combustion, under- sooting, puffback of hot gases, oil leakage and fi...
  • Page 6: Igniter Maintenance

    (b) securing the escutcheon plate to the burner housing. D. Servicing Nozzle Line Assembly A Beckett T650 gauge should be used to set the Z dimension. Before proceeding, turn off power to the burner. Place the end of a ruler at the face of the nozzle and,...
  • Page 7: Fuel Supply

    Section: Fuel Supply Fuel Supply A. Connect Fuel Lines B. Fuel Supply Level with or Above Burner For oil supply system specifi cations for tanks not mounted on machines, carefully follow the pump manufacturer’s Pumps with automatic bypass do literature and the latest edition of the National Fire not require a bypass plug.
  • Page 8: Burner Wiring

    Section: Burner Wiring Burner Wiring Electrical Shock Hazard Explosion, Fire, Scald, & Electrical shock can cause severe personal injury or death. Burn Hazard Remove all jewelry, such as rings and watches before All heating equipment must have HIGH performing service. LIMIT controls to protect against excessive Disconnect electrical power before installing or temperature and/or pressure.
  • Page 9: Drive Component Maintenance

    10% of the rated current. Mounting Position Beckett CleanCut pump may be mounted in any position To replace the burner motor, coupling and/or blower wheel (except upside-down in a single pipe installation).
  • Page 10: Solenoid Valve Testing

    Section: Start Up Burner & Set Combustion C. Solenoid Valve Testing To check solenoid operation, perform the following. Explosion and Fire Hazard Check for oil fl ow and operating pressure by removing the copper tubing from the nozzle line Failure to follow these instructions could and installing a pressure gauge in the line.
  • Page 11: Maintain & Service Burner

    D. Regular Service/Maintenance on the air band and air shutter. Start and stop the burner several times to ensure satisfactory operation. Use only Beckett replacement parts for continued safe operation of the Test the equipment safety controls to verify that burner.
  • Page 12: Troubleshooting

    Section: Troubleshooting □ Clean the blower wheel, air inlet, air guide, retention Table 2. Nozzle Flow Rate by Size head and static plate of any dirt, asphalt or other Nozzle fl ow rate U. S. gallons per hour of No. 2 fuel material.
  • Page 13 Section: Troubleshooting Table 3. Troubleshooting Chart Symptom Possible Cause If the burner is not igniting, the burner motor, drive coupling, and oil pump are operating and oil is fl owing to the nozzle through the solenoid valve, check the following possibilities. Check the air shutter adjustment.
  • Page 14: Replacement Parts

    Oil Valve 22246 Flange Mounting Gasket Specify Tune-up Kit for 30 and 35 Air Brass Elbow 2256 Not Shown 578730 Tube lengths Cord Set, Valve 21807 Splined Nut 3666 * ‘X’s indicate timing options. Contact Beckett for available part numbers.
  • Page 15 24 Vdc SDC Burner Manual...
  • Page 16: Limited Warranty Information

    DAMAGE OF ANY NATURE. Beckett neither assumes, nor authorizes any person to assume for Beckett, any other liability or obligation in connection with the sale of this equipment. Beckett’s liability and Customer’s exclusive remedy is limited to the cost of the product.