Technical specifications
SIPART PS2 PA
Explosion protection to
ATEX
Mounting location
Permissible ambient temperature for
operation
At ≤ -10 °C (+14 °F) the display refresh
rate of the LCD is limited.
(for basic devices with Ex protection
the following applies: Only T4 is per-
module.)
missible when using I
y
Electrical data
Input
Power supply (terminals 6/7)
Bus voltage
• Bus connection with supply unit
- Max. supply voltage U
o
- Max. short-circuit current I
- Max. power P
o
• Bus connection with barrier
- Max. supply voltage (U
)
o
- Max. short-circuit current (I
- Max. power P
o
Current consumption
Additional fault current
Effective internal inductance L
Effective internal capacitance C
Safety shutdown can be activated with
coding bridge (terminals 81/82; elec-
trically isolated from the basic device)
• Input resistance
• Signal status "0" (shutdown active)
• Signal status "1" (shutdown not ac-
tive)
• Effective Internal capacitance C
• Effective internal inductance L
• For connection to power supply with –
- Max. supply voltage U
i
- Max. short-circuit current I
- Maximum power P
i
Electrical isolation
Test voltage
© Siemens AG 2008
Basic device
without Ex protection
Without
-30 ... +80 °C
(-22 ... +176 °F)
Bus-supplied
9 ... 32 V
o
)
o
11.5 mA ± 10%
0 mA
i
i
> 20 kΩ
0 ... 4.5 V or unused
13 ... 30 V
i
i
i
Between basic device
and the input for safety
shutdown, as well as the
outputs of the option
modules
840 V DC, 1 s
Electropneumatic positioners
Basic device
Basic device
with Ex d protection
with Ex ia/ib protection
(flameproof casing)
Ex d
Ex ia/ib
II 2 G Ex d II C T4/T5/T6
II 2 G Ex ia/ib II C T6
Zone 1
Zone 1
T4: -30 ... +80 °C
T4: -30 ... +80 °C
(-22 ... +176 °F)
(-22 ... +176 °F)
T5: -30 ... +65 °C
T5: -30 ... +65 °C
(-22 ... +149 °F)
(-22 ... +149 °F)
T6: -30 ... +50 °C
T6: -30 ... +50 °C
(-22 ... +122 °F)
(-22 ... +122 °F)
Bus-supplied
Bus-supplied
9 ... 32 V
9 ... 24 V
Intrinsically safe
FISCO
17.5 V
380 mA
5.32 W
intrinsically safe
24 V
250 mA
1.2 W
11.5 mA ± 10%
11.5 mA ± 10%
0 mA
0 mA
8 μH
Negligible
> 20 kΩ
> 20 kΩ
0 ... 4.5 V or unused
0 ... 4.5 V or unused
13 ... 30 V
13 ... 30 V
Negligible
Negligible
Intrinsically safe
30 V
100 mA
1 W
Between basic device
The basic device and the
and the input for safety
input to the safety shut-
shutdown, as well as the
down, as well as the out-
outputs of the option
puts of the option
modules
modules, are individual,
intrinsically-safe circuits
840 V DC, 1 s
840 V DC, 1 s
SIPART PS2
Technical specifications
SIPART PS2 PA
Basic device
with Ex n/dust protec-
tion
Ex n
II 3 G Ex nA nL[nL] IIC T6
Dust
II 3 D Ex tD A22 IP66
T100°C
Zone 2/22
T4: -20 ... +75 °C
(-4 ... +167 °F)
T5: -20 ... +65 °C
(-4 ... +149 °F)
T6: -20 ... +50 °C
(-4 ... +122 °F)
Bus-supplied
9 ... 32 V
at "nA" and "tD":
Un = 32 V DC
at "nL":
FNICO
17.5 V
570 mA
at "nL"
32 V
11.5 mA ± 10%
0 mA
8 μH (at "nL")
Negligible
> 20 kΩ
0 ... 4.5 V or unused
13 ... 30 V
Negligible
Negligible
At "nA", "nL" and "tD"
30 V
100 mA
Between basic device
and the input for safety
shutdown, as well as the
outputs of the option
modules
840 V DC, 1 s