Appendix 3: Parameter list level 1 (Pr1)

Legend
L1 = Parameter in Level 1 (without password)
L2 = Parameter in Level 2 (with password = 3 2 1)
N.V. = Parameter not accessible
NOTE: When changing parameter C05 (LS) a reset of the controller (interruption of power supply) is required.
Parameters
Description
ZXDE
ZXDI
C07
rEF
Refrigerant selection for regulation
C16
StC
Digital compressor setpoint
C17
Pbd
Proportional band for compressor regulation
C21
tdG
Cycle time for digital compressor
C24
PMi
Minimum capacity for digital compressor
C25
PMA
Maximum capacity for digital compressor
D29
LPA
Low-pressure alarm value
Condenser temperature setpoint when fan
E39
FSP
setpoint modulation is disabled
E46
Fbd
Regulation band of variable fan
N01
Min
Current minute
N02
Hr
Current hour
N03
MdY
Date of month
N04
Mon
Month
N05
YEr
Year
T18
PAS
Access to Pr2 level
Table 25: Parameters level 1
C6.1.10/0118-0318/E
Range
R404A (0-404) - R507 (1-507) -
R134a (2-134) - R22 (3-R22) -
R407C (4-07C) - R407A (5-07A) -
R407F (6-07F) – R448A (7-48A) -
R449A (8-49A) - R410A (9-410)
LS to US; C03 to C04
0.1 to 9.9 bar; 0.1 to 99.9 PSI;
1 to 999 KPA; 0.1°C to 25.5°C
10 to 40 sec
0 to PMA; 0 to C25
PMi to 100; C24 to 100
0 to 15 bar
-40°C to 110°C
0.1°C to 25.5°C
0 to 59
0 to 23
1 to 31
1 to 12
0 to 99
[0÷999]
ZXDI
L1
L1
L1
L1
L1
L1
L1
L1
L1
L1
L1
L1
L1
L1
L1
36