affected are the main terminal strip and the compressor contactor. It is suggested to check the
main electrical terminations for tightness and to carry out a visual inspection of the low voltage
crimped terminals at least once every 6 months.
5.4

Routine leak testing

NOTE: In order to meet the requirements of the Ecodesign Directive 2009/125/EC with
regard to efficient system operation, ensure the refrigerant and oil charges are sufficient.
All joints inside the system should be leak-tested as part of a regular maintenance schedule.
5.5
Condenser fans & motors
A yearly inspection of these items is recommended. Fastenings can become loose, bearings may
wear and fans may require cleaning of solid deposits that can cause rotational imbalance. Motors
come with lifelong lubrication bearings that do not require lubricating on a routine basis, but just
need to be checked for wear.
In case the fan(s) need(s) to be replaced or serviced, follow the steps below:
De-energize the condensing unit before any intervention.
Remove the top cover of the unit.
Disconnect the air ducts from the fans in order to be able to access the unit front panel.
Remove the entire front panel of the unit to access the condenser fans.
Replace/service the fan(s).
6
Certification & approval
Copeland EazyCool ZXDI indoor condensing units comply with the Low Voltage Directive
LVD 2014/35/EU. The applied harmonised standard is EN 60335-2-891 (Safety Household
and Similar Electrical Appliance, Part 2: Requirements for commercial refrigerating appliances
with an incorporated or remote refrigerant condensing unit or compressor).
The piping complies with the Pressure Equipment Directive PED 2014/68/EU (Art.3 §3 -
Sound Engineering Practice).
The condensing units and their components are CE marked as far as required and thereby
establish conformity with the relevant directives.
Conformity Declarations for components are available as far as required.
The Manufacturer's Declaration of Incorporation has to be respected when incorporating these
products into a machine.
7
Dismantling & disposal
Removing oil and refrigerant:
regulations.
and regulations.
32
Do not disperse in the environment.
Use the correct equipment and method of removal.
Dispose of oil and refrigerant according to national legislation and
Dispose of compressor and/or unit according to national legislation
C6.1.10/0118-0318/E